2014-04-03 14:23:19 | 14030818 |
| 526 CLEMATIS ST. |
| INTERIOR RENOVATION |
| |
| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| REVIEW COMMENTS. |
| |
| SHOW THE LOCATION OF ALL ELECTRICAL SERVICES WITH MAIN |
| DISCONNECTS WHICH ARE SERVING THIS LOCATION. INCLUDE AN |
| ELECTRICAL DEMOLITION PLAN FOR THE ANY EXISTING SERVICE |
| OR INTERIOR ELECTRIC BEING RENOVATED. NEC 230.2, |
| 230.71, 230.72 |
| |
| SHOW THE FEEDERS AND LOCATION FOR ALL MECHANICAL |
| EQUIPMENT CIRCUITS AND DISCONNECTS. NEC 215.5 |
| |
| VERIFY THE EXISTING OCCUPANCY AND PANEL SCHEDULE |
| INCLUDE THE SHOW WINDOW LIGHTING AND A SIGN CIRCUIT. |
| NEC 210.62; 600.5 |
| |
| VERIFY THE ELECTRICAL SERVICE MAINS SERVING THIS |
| BUILDING ARE SIX OR LESS AND GROUPED IN ONE LOCATION. |
| NEC 230.2, 230.71, 230.72 |
| |
| SHOW ALL METERS, GROUNDING, MAIN DISCONNECTS, FEEDERS |
| AND PANEL BOARDS FOR THE BUILDING SERVICE INCLUDING ALL |
| OTHER EXISTING OCCUPANCIES REQUIRING ELECTRICAL |
| SERVICE. |
| NEC 215.5, 230.2, 230.71, 230.72 |
| |
| VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A |
| FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL |
| CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 |
| |
| VERIFY THE ELECTRICAL SERVICE LOAD IS NOT LESS THAN THE |
| SUM OF ALL LOADS AS REQUIRED. NEC 215.5; 220.40 |
| |
| PROVIDE A SUMMARY LOAD CALCULATION. NEC 220.14; 220.40 |
| |
| PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING |
| MEANS. NEC 110.22, 110.16, 110.22 |
| |
| ON THE ELECTRIC PLAN VERIFY AND SHOW ALL REQUIRED |
| ACCESS AND SAFE WORKING CLEARANCES FOR THE ELECTRICAL |
| SERVICE, MAIN DISCONNECT, ELEVATOR CONTROLLERS, |
| ELEVATOR DISCONNECTS AND ALL PANELBOARDS. INCLUDE THE |
| SECOND FLOOR. NEC 110.26; 620.5 |
| |
| INCLUDE THE REQUIRED ELEVATOR BRANCH CIRCUITS ON THE |
| PANEL SCHEDULE AND IN THE LOAD CALCULATION. NEC 110.22; |
| 408.4; 620.23, 620.24 |
| |
| REVISE THE ELECTRIC PANEL DIRECTORY SO THAT ALL |
| CIRCUITS ARE IDENTIFIED AS TO THEIR SPECIFIC PURPOSE OR |
| USE. INCLUDE ALL CIRCUITS FEEDING THE SECOND FLOOR. NEC |
| 408.4 |
| |
| ADD THE EXIT LIGHTING CIRCUIT TO THE LIGHTING PANEL. |
| NEC 408.4 |
| |
| ALL RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS IN THE |
| BAR MUST BE GFCI PROTECTED. NEC 210.8 |
| |
| PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING |
| COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE |
| REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 |
| |
| VERIFY THE REQUIRED GFCI PROTECTED RECEPTACLE IS |
| AVAILABLE TO SERVICE THE MECHANICAL EQUIPMENT. NEC |
| 210.8(B) |
| |
| ON THE ELECTRIC PLAN PROVIDE A LIGHTING SCHEDULE |
| SHOWING FIXTURE SELECTION INCLUDING EXIT LIGHTING WITH |
| BATTERY BACK UP. FBC, ENERGY CONSERVATION 502.3.8; FBC |
| 1011 |
| |
| INDICATE THE LOCATION OF THE ELEVATOR PANELBOARD. NEC |
| 215.5 |
| |
| SHOW REQUIRED RECEPTACLES IN ELEVATOR EQUIPMENT ROOMS |
| AND PITS WITH GFCI PROTECTION. NEC 620.23, 620.85 |
| |
| A SEPARATE BRANCH CIRCUIT SHALL SUPPLY ELEVATOR CAR |
| LIGHTS. NEC 620.22 |
| |
| NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE |
| ELEVATOR, ALARM SYSTEMS, SECURITY AND DATA SYSTEMS. |
| |
| ROBERT LECKY, CBO |
| ELECTRICAL PLANS REVIEW |
| 561-373-3701 |
| |
| |