Plan Review Notes
Plan Review Notes For Permit 14030818
Permit Number 14030818
Review Stop E
Sequence Number 1
Notes
Date Text
2014-04-03 14:23:1914030818
 526 CLEMATIS ST.
 INTERIOR RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 SHOW THE LOCATION OF ALL ELECTRICAL SERVICES WITH MAIN
 DISCONNECTS WHICH ARE SERVING THIS LOCATION. INCLUDE AN
 ELECTRICAL DEMOLITION PLAN FOR THE ANY EXISTING SERVICE
 OR INTERIOR ELECTRIC BEING RENOVATED. NEC 230.2,
 230.71, 230.72
  
 SHOW THE FEEDERS AND LOCATION FOR ALL MECHANICAL
 EQUIPMENT CIRCUITS AND DISCONNECTS. NEC 215.5
  
 VERIFY THE EXISTING OCCUPANCY AND PANEL SCHEDULE
 INCLUDE THE SHOW WINDOW LIGHTING AND A SIGN CIRCUIT.
 NEC 210.62; 600.5
  
 VERIFY THE ELECTRICAL SERVICE MAINS SERVING THIS
 BUILDING ARE SIX OR LESS AND GROUPED IN ONE LOCATION.
 NEC 230.2, 230.71, 230.72
  
 SHOW ALL METERS, GROUNDING, MAIN DISCONNECTS, FEEDERS
 AND PANEL BOARDS FOR THE BUILDING SERVICE INCLUDING ALL
 OTHER EXISTING OCCUPANCIES REQUIRING ELECTRICAL
 SERVICE.
 NEC 215.5, 230.2, 230.71, 230.72
  
 VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A
 FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL
 CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 VERIFY THE ELECTRICAL SERVICE LOAD IS NOT LESS THAN THE
 SUM OF ALL LOADS AS REQUIRED. NEC 215.5; 220.40
  
 PROVIDE A SUMMARY LOAD CALCULATION. NEC 220.14; 220.40
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.22, 110.16, 110.22
  
 ON THE ELECTRIC PLAN VERIFY AND SHOW ALL REQUIRED
 ACCESS AND SAFE WORKING CLEARANCES FOR THE ELECTRICAL
 SERVICE, MAIN DISCONNECT, ELEVATOR CONTROLLERS,
 ELEVATOR DISCONNECTS AND ALL PANELBOARDS. INCLUDE THE
 SECOND FLOOR. NEC 110.26; 620.5
  
 INCLUDE THE REQUIRED ELEVATOR BRANCH CIRCUITS ON THE
 PANEL SCHEDULE AND IN THE LOAD CALCULATION. NEC 110.22;
 408.4; 620.23, 620.24
  
 REVISE THE ELECTRIC PANEL DIRECTORY SO THAT ALL
 CIRCUITS ARE IDENTIFIED AS TO THEIR SPECIFIC PURPOSE OR
 USE. INCLUDE ALL CIRCUITS FEEDING THE SECOND FLOOR. NEC
 408.4
  
 ADD THE EXIT LIGHTING CIRCUIT TO THE LIGHTING PANEL.
 NEC 408.4
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS IN THE
 BAR MUST BE GFCI PROTECTED. NEC 210.8
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 VERIFY THE REQUIRED GFCI PROTECTED RECEPTACLE IS
 AVAILABLE TO SERVICE THE MECHANICAL EQUIPMENT. NEC
 210.8(B)
  
 ON THE ELECTRIC PLAN PROVIDE A LIGHTING SCHEDULE
 SHOWING FIXTURE SELECTION INCLUDING EXIT LIGHTING WITH
 BATTERY BACK UP. FBC, ENERGY CONSERVATION 502.3.8; FBC
 1011
  
 INDICATE THE LOCATION OF THE ELEVATOR PANELBOARD. NEC
 215.5
  
 SHOW REQUIRED RECEPTACLES IN ELEVATOR EQUIPMENT ROOMS
 AND PITS WITH GFCI PROTECTION. NEC 620.23, 620.85
  
 A SEPARATE BRANCH CIRCUIT SHALL SUPPLY ELEVATOR CAR
 LIGHTS. NEC 620.22
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE
 ELEVATOR, ALARM SYSTEMS, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
  
  