2014-04-15 18:59:58 | BUILDING PLAN REVIEW |
| PERMIT: 14030818 |
| ADD: 526 CLEMATIS ST 1ST FLOOR CHANGE OF OCCUPANY/ |
| EXTERIOR ALTERATIONS |
| CONT: JM PROPERTIES OF WEST PALM BEACH, INC |
| TEL: (561)756-5744 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| BLDG TYPE III-B SPRINKLERED |
| |
| 1ST REVIEW |
| DATE: TUESDAY APRIL 16/ 2014 |
| ACTION: DENIED |
| |
| THE LAST RENOVATIONS TO THIS BUILDING UNDER PERMIT |
| 03060274, FIRST FLOOR MERCANTILE AND THE 2ND FLOOR R2 |
| APARTMENTS, THIS REVIEW WILL BE CONSIDERED A CHANGE IN |
| OCCUPANCY AND CHAPTER 9 OF THE EXISITNG BUILDING CODE. |
| 901.3 CHANGE OF OCCUPANCY CLASSIFICATION. |
| WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912 |
| SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| GROUP. |
| |
| 1) THE COVERSHEET A0.0 INDICATES THE 1ST FLOOR |
| OCCUPANCY CLASSIFICATION AS A A-3, THE PLANS APPEAR TO |
| BE A NIGHTCLUB OR BAR / TAVERN WHICH IS A A2 OCCUPANCY, |
| SEE 2010 FBC-B 303.1. |
| |
| 2) THE COVERSHEET A0.0 INDICATES THIS BUILDING TO BE |
| FIRE SPRINKLERED, BUT THERE IS NO MENTION OF A FIRE |
| SPRINKLER PLAN IN THE INDEX OF DRAWINGS NOR ANYWHERE |
| ELSE IN THE PLANS. TRAVEL DISTANCES ARE SHOWN FOR |
| NON-SPRINKLERED BUILDING. |
| 2010 EXST BLDG CODE 904.1 GENERAL. |
| FIRE PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY |
| WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE |
| OF OCCUPANCY CLASSIFICATION. |
| 912.2 FIRE PROTECTION SYSTEMS. |
| FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| WITH SECTIONS 912.2.1 AND 912.2.2. |
| |
| EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. |
| WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE |
| PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| CHANGE OF OCCUPANCY OCCURS. |
| |
| 2010 FBC-B F] 903.2.1.2 GROUP A-2. |
| AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR |
| GROUP A-2 OCCUPANCIES WHERE ONE OF THE FOLLOWING |
| CONDITIONS EXISTS: |
| 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2); |
| 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE; |
| |
| EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION SYSTEM. |
| WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE |
| PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION |
| APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT |
| THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A |
| FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL |
| BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED. |
| |
| 3) SHEET A1.1 SHOWS NEW OUT SWING ENTRY DOORS PLEASE |
| PROVIDE A SURVEY WITH THE DISTANCE FROM THE BUILDING TO |
| THE PROPERTY LINE AT THE CLEMATIS OR FRONT OF THE |
| BUILDING. 2010 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE |
| AND BELOW 8 FEET IN HEIGHT. |
| ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE |
| AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE |
| PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1 |
| THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR |
| PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| |
| 4) SHEET A1.1 FRONT ENTRY AREA THERE IS A DISCREPANCY |
| IN THE PLANS. THE 1ST FLOOR PLAN AND LIFE SAFETY PLAN |
| SHOW TWO SWING ENTRY DOORS AND THE EXTERIOR FOLDING |
| DOOR SYSTEM FOLDING OVER AND STCKING ALL THE WAY TO THE |
| EAST OF THE OPENING, WHERE AS THE STRUCTURAL SHEET S1 |
| SHOWS THE DOORS SPLITTING IN THE CENTER AND FOLDING |
| EACH WAY. THE FOLDING DOOR SYSTEM THAT SPLITS IN THE |
| MIDDLE WILL NOT ALLOW AN ACCESSIBLE ENRY AT THE SWING |
| DOOR SINCE THERE WILL NOT BE 18 INCHES CLEAR AT THE |
| LATCH SIDE OF THE DOOR 2010 FL ACCESS CODE 404.2.4.1 & |
| FIGURE 404.2.4.1(A). |
| |
| 5) THE PLANS DO NOT HAVE ANY DETAILS AS FAR AS THE SILL |
| FOR TTHE FOLDING DOOR SYSTEM, PLEASE PROVIDE COMPLIANCE |
| WITH 2010 FL ACCESS CODE 404.2.5 THRESHOLDS. |
| THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH |
| (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN |
| LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303. |
| |
| 6) SHEET A1.1 THE FRONT EXIT ENCLOSURE BOTH 1ST FLOOR & |
| 2ND FLOOR LANDINGS SHOW THE ELEVATOR LOCATED IN THE |
| EXIT ENCLOSURE. PLEASE REVIEW 2010 FBC-B 1022.3 & |
| 1022.4. |
| 2010 FBC-B 1022.3 |
| EXIT ENCLOSURE OPENING PROTECTIVES SHALL BE IN |
| ACCORDANCE WITH THE REQUIREMENTS OF SECTION 715. |
| |
| OPENINGS IN EXIT ENCLOSURES OTHER THAN UNPROTECTED |
| EXTERIOR OPENINGS SHALL BE LIMITED TO THOSE NECESSARY |
| FOR EXIT ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED |
| SPACES AND FOR EGRESS FROM THE ENCLOSURE. |
| |
| ELEVATORS SHALL NOT OPEN INTO AN EXIT ENCLOSURE. |
| |
| 2010 FBC-B 1022.4 PENETRATIONS. |
| PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT |
| ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, |
| STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING |
| THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT |
| EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| SECTION 713. |
| THERE SHALL BE NO PENETRATIONS OR COMMUNICATION |
| OPENINGS, WHETHER PROTECTED OR NOT, BETWEEN ADJACENT |
| EXIT ENCLOSURES. |
| |
| 6A)(1) 2010 FBC-B 707.3.2 EXIT ENCLOSURES. THE |
| FIRE-RESISTANCE RATING OF THE FIRE BARRIER SEPARATING |
| BUILDING AREAS FROM AN EXIT SHALL COMPLY WITH SECTION |
| 1022.1. |
| |
| 6A)(2) 2010 FBC-B 708.5 CONTINUITY. SHAFT ENCLOSURES |
| SHALL BE CONSTRUCTED AS FIRE BARRIERS IN ACCORDANCE |
| WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| IN ACCORDANCE WITH SECTION 712, OR BOTH, AND SHALL HAVE |
| CONTINUITY IN ACCORDANCE WITH SECTION 707.5 FOR FIRE |
| BARRIERS OR SECTION 712.4 FOR HORIZONTAL ASSEMBLIES AS |
| APPLICABLE. |
| |
| 6A)(3) 2010 FBC-B 707.5 CONTINUITY. FIRE BARRIERS SHALL |
| EXTEND FROM THE TOP OF THE FOUNDATION OR FLOOR/CEILING |
| ASSEMBLY BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF |
| SHEATHING, SLAB OR DECK ABOVE AND SHALL BE SECURELY |
| ATTACHED THERETO. SUCH FIRE BARRIERS SHALL BE |
| CONTINUOUS THROUGH CONCEALED SPACES, SUCH AS THE SPACE |
| ABOVE A SUSPENDED CEILING. SHEET A3.1 DETAIL A1 SHOWS A |
| DETAIL FOR A 1 HR FIRE RATED WALL, BUT THE DETAIL DOES |
| NOT INDICATE HOW IT WILL DEAL WITH A WOOD FLOOR TRUSS |
| SYSTEM, OR HOW THE FIRE RATING MAY OCCUR AROUND |
| HEADERS, AND WOOD BUILT UP FLOOR TRUSS GIRDERS. |
| |
| 7) SHEET A1.1 LIFE SAFETY PLAN IS MISSING THE RATING OF |
| WALLS AND DOORS: |
| 7A) THE FRONT AND REAR STAAIRWELLS DO NOT INDICATTE A 1 |
| HOUR FIRE RATED WALL ALL THE WAY AROUND THE ENCLOSURE, |
| 2010 FBC-B 1022.1 AND THE REQUIRED FIRE RATED DOORS PER |
| 2010 FBC-B 715 & TABLE 715.4 1 HOUR RATED DOORS . |
| |
| 7B) THE ELEVATOR MACHINE ROOM 2010 FBC-B 3006.4. PLEASE |
| NOTTE THE CEILING OF THIS ROOM WILL NEED TO BE FIRE |
| RATED AS WELL IT WILL ABUT THE FRAMING MEMBERS OF THE |
| STAIRWELL. 2010 FBC-B 1022.1 & 707 HORIZONTAL |
| ASSEMBLIES. DOOR RATING 3/4 HR FIRE BARRIER TABLE |
| 715.4. |
| |
| 8) UNDER THE 03060274 PERMIT THE STAIR ENCLOSURE AND |
| ELEVATOR WERE A DIFFERENT CONFIGURATION, THE PLANS DO |
| NOT IDENTIFY ANY CHANGES TO THE FLOOR FRAMING |
| RECONFIGURATION? ADDITIONAL INFORMATION IS REQUIRED, |
| 107.2.1.3. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| EDITION. |
| |
| 9) SHEET A2.1 HAS (3) AREAS WHERE WHITE OUT HAS BEEN |
| USED ON THE PLANS. 107.2.1.4 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 2010 EDITION 2012. QUALITY OF BUILDING |
| PLANS. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. OTHER THAN THE |
| RECONFIGURATION OF THE EXIT ENCLOSURE SHOWS NO WORK TO |
| BE COMPLETED UNDERTHIS PERMIT. |
| |
| |
| |
| 10) STRUCTURAL SHEET S-1: |
| |
| 10A) STRUCTURAL SHEET ELEVATOR DETAIL IS MISSING THE |
| FOLLOWING : |
| 10A)(1) TB- HEIGTH NOT PROVIDED. |
| 10A)(2) B-24 THE HEIGHT OF THE BEAM TOP OR BOTTOM OF |
| BEAM NOT PROVIDED |
| 10A)(3) ELEVATOR DOES NOT SHOW A PIT OR RECESS FOR THE |
| FLOOR OF THE ELEVATOR CAB TO BE LEVEL WITH THE FLOOR. |
| 10)(4) THE ELEVATOR SHAFT DOES NOT CONTINUE THROUGH THE |
| SECOND FLOOR. |
| 10)(5) SHAFT ENCLOSURE, 2010 FBC-B 708.12 ENCLOSURE AT |
| THE TOP. A SHAFT ENCLOSURE THAT DOES NOT EXTEND TO THE |
| UNDERSIDE OF THE ROOF SHEATHING, DECK OR SLAB OF THE |
| BUILDING SHALL BE ENCLOSED AT THE TOP WITH CONSTRUCTION |
| OF THE SAME FIRE-RESISTANCE RATING AS THE TOPMOST FLOOR |
| PENETRATED BY THE SHAFT, BUT NOT LESS THAN THE |
| FIRE-RESISTANCE RATING REQUIRED FOR THE SHAFT |
| ENCLOSURE. |
| |
| |
| 10B) STEEL COLUMNS & W 16X31 BEAM |
| |
| 10B)(1) PLANS CALL FOR 5X5X5/16 OR 5 INCH DIA X ).258 |
| STEEL COLUMNS. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| EDITION 2012 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. |
| |
| 10B)(2) PLANS DO NOT PROVIDE THE SIZE FOR THE COLUMN |
| BASE PLATE NOR TOP PLATE, THICKNESS, MATERIAL NOR THE |
| BOLT LOCATION IN THE PLATE OR IF WELDED. 2010 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION, 2010 EDITION 2012 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH DRAWINGS |
| AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE |
| FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. |
| |
| 10B)(3) NEW BATHROOM BEARING WALL DETAIL.DETAIL # 2 |
| ONLY SHOWS THE BOTTOM OF THE STUD WALL DOES NOT |
| INDICATE IF A SINGLE TOP PLATE IS REQUIRED OR IF DOUBLE |
| TOP PLATE WILL BE REQUIRED? THE OTHER ISSUE IS WILL A |
| STIFFNEER BE REQUIRED AS IN DETAIL # 3 FOR THE NEW |
| CARRYING W 16X31 STEEL BEAM? IF SO WHAT TYPE OF |
| MATERIALS AND NAILING PATTERN. |
| |
| 10C) FRONT ENTRY REDESIGN: |
| 10C)(1) MISSING PRODUCT APPROVALS 2010 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS:(31)(A) EXTERIOR DOORS. |
| |
| 10C)(2) MISSING DIMENSIONS, NO INFORMATION FOR VERTICAL |
| NOR HORIZONTAL STEEL FRAMING MEMBERS, PRODUCT APPROVALS |
| WILL NEED TO BE DECIDED TO BE ABLE TO PRODUCE THE |
| SIZING OF THE ROUGH OPENING. 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 2010 EDITION 107.2.1.3 ADDITIONAL DATA. |
| THE BUILDING OFFICIAL MAY REQUIRE DETAILS, |
| COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA NECESSARY |
| TO DESCRIBE THE CONSTRUCTION OR INSTALLATION AND THE |
| BASIS OF CALCULATIONS. ALL DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA REQUIRED BY THE BUILDING OFFICIAL TO |
| BE PREPARED BY AN ARCHITECT OR ENGINEER SHALL BE |
| AFFIXED WITH THEIR OFFICIAL SEAL, SIGNATURE AND DATE AS |
| STATE LAW REQUIRES. |
| |
| |
| 11) SHEET A3.1 DEATIL # 4 INDICATES THE INSTALATION OF |
| DROP CEILINGS, NOTE # 6 INDICATES THE TYPE OF FASTENERS |
| TO BE USED IF THE INSTALATION IS FOR CONCRETE DECKS BUT |
| NOT FOR WOOD FRAMED TRUSSES WITH METAL HI HAT FRAMING |
| BETWEEN THE 5/8 INCH DRYWALL AND FLOOR TRUSS. 2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1.3 |
| ADDITIONAL DATA. |
| |
| 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |