2014-03-26 17:13:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FASTENER PROPOSED IS NOT CLEAR. "TYPE OF ANCHOR
 SPECIFIED" STATES "2 1/4 X 1/4 POWERS TAPCON"
  
 IN THE COLUMN "SPECIFIC ANCHOR TYPE" IT STTATES:
  
 1/4 POWERS
 TAPCON
  
 ALL OTHER COLUMNS HAVE TWO SETS OF DATA; ONE FOR TOP,
 ONE FOR BOTTOM. SO, IT APPEARS THAT THIS IS TO MEAN
 POWERS TAPPER ON THE TOP, TAPCON ON THE BOTTOM. THE
 SHEETS WITH THE ANCHOR CHARTS WERE NOT SUBMITTED
 (PRODUCT APPROVAL INCOMPLETE) BUT IN OTHER REVIEWS
 CONTRACTOR WAS INFORMED THAT TAPCON SPACING NOT
 COMPLIANT.
  
 IF CONTRACTOR PROPOSES POWERS TAPPERS TOP AND BOTTOM,
 PLEASE CLARIFY AS TO WHY THE INSTALLATION SCHEDULE
 REFERS TO "TAPCONS" IN TWO PLACES.
  
 2. PRODUCT APPROVAL INCOMPLETE. PROVIDE ALL SHEETS SO A
 COMPLETE REVIEW CAN BE PERFORMED.
  
  
  
  