Plan Review Notes For Permit 14030575 |
Permit Number |
14030575 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-03-21 15:32:08 | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO | | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. | | | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | FEET OF EACH SLEEPING ROOM. | | | | NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES. | | | | FBC- 107.3.5.3 PROVIDE MORE ELECTRICAL INFOMATION TO | | DEMONSTRATE ADEQUATE SERVICE CAPACITY, CIRCUITS, WIRE | | SIZE, WIRING METHOD, OVERCURRENT PROTECTION. |
|