Plan Review Notes
Plan Review Notes For Permit 14030562
Permit Number 14030562
Review Stop B
Sequence Number 2
Notes
Date Text
2014-06-06 17:42:45BUILDING PLAN REVIEW
 PERMIT: 14030562
 ADD: 1875 PALM BCH LAKES # A09
 CONT: TO BE DETERMINED
 TEL: (561)373-3902 / KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRIDAY JUNE 06/2014
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) PB OUTLET MALLS:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 3A) COMPLIED.
  
 3B) NOTE TO DESIGNER!!!: CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED THREE OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 2ND REQUEST!!!THE PLANS, LIFE SAFETY SHEET A1.0 ARE
 INDICATING THEY ARE TAKING AREA INCREASES FOR FIRE
 SPRINKLERS, THE INDEX AND PLANS FAIL TO CONTAIN FIRE
 SPRINKLER & FIRE ALARM PLANS WITHIN THIS SET.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 (5) . FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERSFIRE SPRINKLER PLANS ARE A
 MUST, OVER 12,000 SQ FT. SHEET A1.0 INDICATE A AREA
 INCREASE OF 300% WITH
 FIRE SPRINKLERS, THERE ARE NO FIRE SPRINKLER PLANS
 LISTED IN THE INDEX NOR IS THERE A SEPARATE SET OF FIRE
 SPRINKLER PLANS SUBMITTED WITH THE 2ND SUBMITTAL.
  
 SECTION NOT MET: 2010 FBC-B F] 903.2.7 GROUP M. AN
 AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT
 BUILDINGS CONTAINING A GROUP M OCCUPANCY WHERE ONE OF
 THE FOLLOWING CONDITIONS EXISTS: 1. A GROUP M FIRE AREA
 EXCEEDS 12,000 SQUARE FEET (1115 M2).
  
 3C) COMPLIED.
  
 4) 2ND REQUEST, BUILDING EVALUATION IS STILL LOW. THE
 ICC TABLES PUT THE BUILDING TYPE IIB AT $115.47 SQ FT.
 THE SHELL'
 ROOF & FIRE SPRINKLERS TOTAL COST COMES TO $44.00 A
 SQUARE FOOT OR THE TENANT BUILD OUT WITH THE FIRE
 SPRINKLERS FOR THE TENANT BUILD OUT INCLUDED AT $71.00
 A SQUARE FOOT.
 THE TENANT BUILD OUT VALUE IS LOW AT $18.64 DOLLARS /
 SQ FT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF
 PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 5-7) COMPLIED.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  