Date |
Text |
2014-04-14 17:47:04 | PLUMBING PLAN REVIEW |
| PERMIT: 14030562 |
| ADD: 1875 PALM BCH LAKES # A09 |
| CONT: TO BE DETERMINED |
| TEL: (561)373-3902 / KARI |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: MONDAY APRIL 14/ 2014 |
| ACTION: DENIED |
| |
| 1) SHEET P1.1 PLEASE PROVIDE THE MANUFACTURERS SPEC |
| SHEETS FOR THE FOLLOWING PLUMBING FIXTURES; |
| |
| 1A) TRENCH DRAINS AND IN ACCORDANCE WITH 2010 FBC-P |
| 412.1 APPROVAL. |
| TRENCH DRAINS SHALL COMPLY WITH ASME A112.6.3. |
| |
| 1B) IT-1 GOOSE NECK W/ 8'-0" VINYL HOSE 2010 FBC-P |
| 424.6 HOSE-CONNECTED OUTLETS. |
| FAUCETS AND FIXTURE FITTINGS WITH HOSE-CONNECTED |
| OUTLETS SHALL CONFORM TO ASME A112.18.3M OR CSA B125. |
| |
| 1C) OXY 1-3 HJC VENDOR CUT SHEETS 2010 FBC-P 1201.1 |
| SCOPE. |
| THE PROVISIONS OF THIS CHAPTER SHALL GOVERN THE DESIGN |
| AND INSTALLATION OF PIPING AND STORAGE SYSTEMS FOR |
| NONFLAMMABLE MEDICAL GAS SYSTEMS AND NONMEDICAL OXYGEN |
| SYSTEMS. ALL MAINTENANCE AND OPERATIONS OF SUCH SYSTEMS |
| SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION |
| CODE. |
| PLEASE PROVIDE A MED-GAS PLAN FOR THE OXYGEN UNDER A |
| SEPERATE PERMIT. DETAILS CAN BE ONTHIS PLAN. REQUIRES A |
| DIFFERNT PERMIT, BECAUSE OF THE INSPECTION CODES ARE |
| DIFFERENT FROM THE PLUMBING. |
| |
| 1D) SB1, SB2 & SB3 SCAVENGER VACCUUM UNIT , DROPS AND |
| WET TABLE OUTLETS. PLEASE PROVIDE THE MANUFACTURERS CUT |
| SHEETS ON THEASE PRODUCTS. 2010 FBC-P 713.4 OR 713.5. |
| THE PLANS DO NOT PROVIDE A CLEAR VIEW OF THE SCAVENGER |
| VACCUUM UNIT AND PIPING LAYOUT NOR DOES THE PLANS |
| INDICATE WHERE THE VENT ON THE PUMP IS GOING TO VENT |
| TO. THE EXHAUSTS FROM A VACUUM PUMP SERVING A VACUUM |
| (FLUID SUCTION) SYSTEM SHALL DISCHARGE SEPARATELY TO |
| OPEN AIR ABOVE THE ROOF. 713.6. |
| |
| 2) SHEET P0.1 HEADING PB-7 2 /250 OXYGEN CYLINDERS |
| PROVIDE DETAIL FOR SECURING TO WALL AND FOR THE |
| MANIFOLD. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |