Plan Review Notes
Plan Review Notes For Permit 14030562
Permit Number 14030562
Review Stop M
Sequence Number 1
Notes
Date Text
2014-04-18 07:51:28PLAN DENIED
 1) PROVIDE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS ON THE ELECTRIC UNIT HEATER.
 PER SECTION 107 FBC 2010
 2) REFER TO SECTION 604.8 LINING
 INSULATION. 2010 FBC (M)
 3) REFER TO SECTION 503.2.1 CALCULATION OF
 HEATING AND COOLING. FLORIDA ENERGY CODE 2010
 4) REFER TO SECTION 503.2.4.4 SHUTOFF
 DAMPER CONTROLS. FLORIDA ENERGY CODE 2010
 PLAN REVIEW BY HAROLD MOSER