| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| REVIEW COMMENTS. |
| |
| PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN |
| DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22 |
| |
| PROVIDE DEDICATED EQUIPMENT SPACES WITH SAFE WORKING |
| CLEARANCE AND DIMENSIONS FOR THE SWITCH BOARDS AND |
| PANEL BOARDS. 110.26 |
| |
| PROVIDE SPECIFICATIONS AND LISTING FOR HILL PHOENIX |
| ELECTRICAL EQUIPMENT SPECIFIED. VERIFY THIS EQUIPMENT |
| IS MARKED AS SUITABLE FOR USE AS SERVICE EQUIPMENT. NEC |
| 110.3, 230.66 |
| |
| PROVIDE DETAILS OF ALL ELECTRICAL SERVICES PROPOSED FOR |
| THIS BUILDING (BUILDING ?A?). THE MASTER PLAN LIMITS |
| THE NUMBER OF MAIN DISCONNECTS TO FOUR WHICH MUST BE |
| GROUPED IN ONE LOCATION. NEC 230.2; 230.40; 230.70; |
| 230.71 |
| |
| PROVIDE CALCULATIONS CLARIFYING THE SELECTION OF |
| PRIMARY AND SECONDARY PROTECTION FOR TRANSFORMER ?T?. |
| NEC 450.3(B) |
| |
| SHOW LOCATION OF THE MAIN DISCONNECTS FOR THE PANELS |
| FED FROM TRANSFORMER (T1). VERIFY DISCONNECTS ARE |
| GROUPED. VERIFY THE TAP CONDUCTORS ARE THE APPROPRIATE |
| LENGTH. NEC 240.21, 450.3 (B); 240.4(F); 240.21(C) |
| |
| PANEL ?LA? REQUIRES A LARGER FEEDER. NEC 240.4; 240.6; |
| T. 310.16 |
| |
| PROVIDE SPECIFICATIONS AND LISTING FOR THE 400 AMP |
| SERVICE RATED MAIN DISCONNECT. NEC 110.3 |
| |
| PROVIDE SPECIFICATIONS FOR THE GENERATOR TRANSFER |
| SWITCH. INCLUDE A GENERATOR DISCONNECT, LOAD |
| CALCULATION, LOCATION SIGNAGE, GROUNDING AND FEEDER |
| SIZE. NEC 215.5; 445.13; 445.18; 702.5; 702.8; 702.10 |
| |
| PROVIDE SPECIFICATIONS AND LISTING FOR THE X-RAY |
| EQUIPMENT AND DISCONNECT. NEC 110.3 |
| |
| PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF ROOF TOP |
| EQUIPMENT. NEC 210.8; 210.63 |
| |
| SHOW THE LIGHTING BRANCH CIRCUITS ON THE LIGHTING FLOOR |
| PLAN. NEC 210.11 |
| |
| PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING |
| COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE |
| REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; 505.5.3; T |
| 505.5.3 |
| |
| PROVIDE OR CONFIRM THAT THE INTERIOR AND EXTERIOR |
| LIGHTING CONTROLS PROVIDED ARE IN ACCORDANCE WITH THE |
| FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL |
| BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME |
| SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST |
| 10 HOURS. FBC ENERGY CONSERVATION 505.2 |
| |
| PROVIDE LIGHTING CONTROLS ON THE SIGN CIRCUIT. |
| AUTOMATIC CONTROLS SHALL BE CAPABLE OF RETAINING |
| PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER |
| FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY |
| CONSERVATION 505.2 |
| |
| CONDUCTORS FOR DATA AND COMMUNICATIONS SYSTEMS LOCATED |
| AT OR BELOW GRADE MUST BE LISTED AS SUITABLE FOR DAMP |
| OR WET LOCATIONS. NEC 110.3, 110.8, |
| |
| |
| NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE |
| ALARM SYSTEMS, SECURITY, VOICE, DATA SYSTEMS, AND |
| GENERATOR. |
| |
| |