 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22
  
 PROVIDE DEDICATED EQUIPMENT SPACES WITH SAFE WORKING
 CLEARANCE AND DIMENSIONS FOR THE SWITCH BOARDS AND
 PANEL BOARDS. 110.26
  
 PROVIDE SPECIFICATIONS AND LISTING FOR HILL PHOENIX
 ELECTRICAL EQUIPMENT SPECIFIED. VERIFY THIS EQUIPMENT
 IS MARKED AS SUITABLE FOR USE AS SERVICE EQUIPMENT. NEC
 110.3, 230.66
  
 PROVIDE DETAILS OF ALL ELECTRICAL SERVICES PROPOSED FOR
 THIS BUILDING (BUILDING ?A?). THE MASTER PLAN LIMITS
 THE NUMBER OF MAIN DISCONNECTS TO FOUR WHICH MUST BE
 GROUPED IN ONE LOCATION. NEC 230.2; 230.40; 230.70;
 230.71
  
 PROVIDE CALCULATIONS CLARIFYING THE SELECTION OF
 PRIMARY AND SECONDARY PROTECTION FOR TRANSFORMER ?T?.
 NEC 450.3(B)
  
 SHOW LOCATION OF THE MAIN DISCONNECTS FOR THE PANELS
 FED FROM TRANSFORMER (T1). VERIFY DISCONNECTS ARE
 GROUPED. VERIFY THE TAP CONDUCTORS ARE THE APPROPRIATE
 LENGTH. NEC 240.21, 450.3 (B); 240.4(F); 240.21(C)
  
 PANEL ?LA? REQUIRES A LARGER FEEDER. NEC 240.4; 240.6;
 T. 310.16
  
 PROVIDE SPECIFICATIONS AND LISTING FOR THE 400 AMP
 SERVICE RATED MAIN DISCONNECT. NEC 110.3
  
 PROVIDE SPECIFICATIONS FOR THE GENERATOR TRANSFER
 SWITCH. INCLUDE A GENERATOR DISCONNECT, LOAD
 CALCULATION, LOCATION SIGNAGE, GROUNDING AND FEEDER
 SIZE. NEC 215.5; 445.13; 445.18; 702.5; 702.8; 702.10
  
 PROVIDE SPECIFICATIONS AND LISTING FOR THE X-RAY
 EQUIPMENT AND DISCONNECT. NEC 110.3
  
 PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF ROOF TOP
 EQUIPMENT. NEC 210.8; 210.63
  
 SHOW THE LIGHTING BRANCH CIRCUITS ON THE LIGHTING FLOOR
 PLAN. NEC 210.11
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; 505.5.3; T
 505.5.3
  
 PROVIDE OR CONFIRM THAT THE INTERIOR AND EXTERIOR
 LIGHTING CONTROLS PROVIDED ARE IN ACCORDANCE WITH THE
 FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL
 BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. FBC ENERGY CONSERVATION 505.2
  
 PROVIDE LIGHTING CONTROLS ON THE SIGN CIRCUIT.
 AUTOMATIC CONTROLS SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY
 CONSERVATION 505.2
  
 CONDUCTORS FOR DATA AND COMMUNICATIONS SYSTEMS LOCATED
 AT OR BELOW GRADE MUST BE LISTED AS SUITABLE FOR DAMP
 OR WET LOCATIONS. NEC 110.3, 110.8,
  
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE
 ALARM SYSTEMS, SECURITY, VOICE, DATA SYSTEMS, AND
 GENERATOR.
  
  