Plan Review Notes
Plan Review Notes For Permit 14030522
Permit Number 14030522
Review Stop B
Sequence Number 1
Notes
Date Text
2014-04-09 14:28:072010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND
 THE PLANS SPECIFY EXPOSURE B. PLEASE REVISE PLANS AND
 WIND LOAD PRESSURES AS NECESSARY. FBC R301.2.1
  
 2) THE NAME AND SIGNATURE OF THE PERSON THAT IS
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS.
 CITY AMENDMENTS 107,2,1
  
 3) THE ENERGY CALCULATION FORM SPECIFIES THAT THIS IS
 NEW CONSTRUCTION WHEN IT IS AN EXISTING HOUSE UNDER
 GOING A REMODEL. PLEASE CORRECT.
  
 4) THE PRODUCT APPROVAL FOR THE ENTRY DOOR WITH
 SIDELITE ( FL15225 ) SPECIFIES THAT THE SIDELITE IS NOT
 IMPACT RATED. THEREFORE, THE SIDELITE WILL REQUIRE AN
 IMPACT PROTECTION DEVICE. SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE STORM PANELS FOR THIS OPENING WITH AN
 INSTALLATION SCHEDULE SPECIFYING THE ANCHORS, ANCHOR
 SPACING, SPAN, ETC. FBC R301.2.1.2 AND DCA RULE 9N-3
  
 5) SUBMIT TWO SETS OF SIGNED AND SEALED RAS117
 CALCULATIONS FOR THE LOW SLOPE ROOF GAF MODIFIED SYSTEM
 ( NOA 13-0424.14 ). THE SIGNED AND SEALED P.B.C.
 ROOFING FORM 100 IS RAS 117 CALCULATIONS AS REQUIRED BY
 LIMITATION #7 OF THE NOA AND IS NOT ACCEPTABLE. FBC
 R301.2.1.2 AND CITY AMENDMENTS 107.2.1.3
  
 6) THE DRIVEWAY AND SCREEN ROOM ARE REQUIRED TO BE
 SUBMITTED AS SEPARATE PERMITS. SEPARATE PERMITS,
 APPLICATIONS AND REVIEWS ARE REQUIRED. NOTE: THE
 PRODUCT APPROVALS FOR THE SCREEN ROOM ROOF PANELS WILL
 NEED TO BE SUBMITTED.
  
 7) IN ORDER TO REDUCE REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER WITH YOUR RE-SUBMITTAL.
  
 PLEASE DO NOT STAPLE PRODUCT APPROVALS AND OTHER ITEMS
 TO THE PLANS.