2014-04-09 14:28:07 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND |
| THE PLANS SPECIFY EXPOSURE B. PLEASE REVISE PLANS AND |
| WIND LOAD PRESSURES AS NECESSARY. FBC R301.2.1 |
| |
| 2) THE NAME AND SIGNATURE OF THE PERSON THAT IS |
| RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS. |
| CITY AMENDMENTS 107,2,1 |
| |
| 3) THE ENERGY CALCULATION FORM SPECIFIES THAT THIS IS |
| NEW CONSTRUCTION WHEN IT IS AN EXISTING HOUSE UNDER |
| GOING A REMODEL. PLEASE CORRECT. |
| |
| 4) THE PRODUCT APPROVAL FOR THE ENTRY DOOR WITH |
| SIDELITE ( FL15225 ) SPECIFIES THAT THE SIDELITE IS NOT |
| IMPACT RATED. THEREFORE, THE SIDELITE WILL REQUIRE AN |
| IMPACT PROTECTION DEVICE. SUBMIT TWO COPIES OF PRODUCT |
| APPROVALS FOR THE STORM PANELS FOR THIS OPENING WITH AN |
| INSTALLATION SCHEDULE SPECIFYING THE ANCHORS, ANCHOR |
| SPACING, SPAN, ETC. FBC R301.2.1.2 AND DCA RULE 9N-3 |
| |
| 5) SUBMIT TWO SETS OF SIGNED AND SEALED RAS117 |
| CALCULATIONS FOR THE LOW SLOPE ROOF GAF MODIFIED SYSTEM |
| ( NOA 13-0424.14 ). THE SIGNED AND SEALED P.B.C. |
| ROOFING FORM 100 IS RAS 117 CALCULATIONS AS REQUIRED BY |
| LIMITATION #7 OF THE NOA AND IS NOT ACCEPTABLE. FBC |
| R301.2.1.2 AND CITY AMENDMENTS 107.2.1.3 |
| |
| 6) THE DRIVEWAY AND SCREEN ROOM ARE REQUIRED TO BE |
| SUBMITTED AS SEPARATE PERMITS. SEPARATE PERMITS, |
| APPLICATIONS AND REVIEWS ARE REQUIRED. NOTE: THE |
| PRODUCT APPROVALS FOR THE SCREEN ROOM ROOF PANELS WILL |
| NEED TO BE SUBMITTED. |
| |
| 7) IN ORDER TO REDUCE REVIEW TIME, PLEASE SUBMIT A |
| RESPONSE LETTER WITH YOUR RE-SUBMITTAL. |
| |
| PLEASE DO NOT STAPLE PRODUCT APPROVALS AND OTHER ITEMS |
| TO THE PLANS. |