Plan Review Notes For Permit 14030475 |
Permit Number |
14030475 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-03-13 14:39:46 | ROOF RECOVER, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- SINGLE PLY ROOFING SYSTEM NOA 12-0605.04 SUBMITTED | | WAS SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE | | WEBSITE AND DOWNLOAD CURRENT NOA. RESUBMIT CURRENT NOA. | | NEED CURRENT PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | 9N-3. | | | | 2- A) PROVIDE FASTENER UPLIFT TEST USING THE TESTING | | APPLICATION STANDARD TAS 105 AS REQUIRED BY GENERAL | | LIMITATIONS #5 AND #6 OF NOA SUBMITTED. | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | REQUIRED BY GENERAL LIMITATION #5 AND #6 OF NOA | | SUBMITTED. NEED ITEMS 2(A) AND 2(B) ABOVE TO MEET THE | | DESIGN PRESSURES OF SEC. 1609 OF FBC-2010. | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION WAS | | UPDATED TO $87,498. THE ADJUSTED PERMIT FEE BALANCE IS | | $2190.35. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|