Plan Review Notes
Plan Review Notes For Permit 14030475
Permit Number 14030475
Review Stop B
Sequence Number 1
Notes
Date Text
2014-03-13 14:39:46ROOF RECOVER, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- SINGLE PLY ROOFING SYSTEM NOA 12-0605.04 SUBMITTED
 WAS SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE
 WEBSITE AND DOWNLOAD CURRENT NOA. RESUBMIT CURRENT NOA.
 NEED CURRENT PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9N-3.
  
 2- A) PROVIDE FASTENER UPLIFT TEST USING THE TESTING
 APPLICATION STANDARD TAS 105 AS REQUIRED BY GENERAL
 LIMITATIONS #5 AND #6 OF NOA SUBMITTED.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #5 AND #6 OF NOA
 SUBMITTED. NEED ITEMS 2(A) AND 2(B) ABOVE TO MEET THE
 DESIGN PRESSURES OF SEC. 1609 OF FBC-2010.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION WAS
 UPDATED TO $87,498. THE ADJUSTED PERMIT FEE BALANCE IS
 $2190.35.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712