Plan Review Notes For Permit 14030441 |
Permit Number |
14030441 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-03-13 16:44:09 | CODE: 2010 FBC. | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR: | | A) ROOF TILE ADHESIVE. NOA 12-0228.18 SUBMITTED WAS | | SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA. VISIT | | MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. | | | | B) ATTIC FAN. POWER ROOF VENT NOA 12-1102.01 SUBMITTED | | IS FOR SHINGLES INSTALLATION ONLY. SEE GENERAL | | LIMITATION #3 ON LAST PAGE OF NOA SUBMITTED. NEED | | PRODUCT APPROVAL FOR ATTIC FAN FOR CONCRETE TILE | | INSTALLATION. | | | | 2- VALUATION SPECIFIED IN THE PERMIT APPLICATION IS TOO | | LOW FOR THE PROPOSED SCOPE OF WORK. SEC. 109.3 CITY | | AMENDMENTS TO FBC. VALUATION TO INCLUDE ALL LABOR AND | | MATERIALS, INCLUDING THE THREE SKYLIGHTS AND THE | | POWERED ATTIC FAN. | | | | | | ***NOTE: NEED ELECTRICAL PERMIT FOR THE POWER ROOF VENT | | INSTALLATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|