2014-03-26 08:42:21 | BUILDING PLAN REVIEW |
| PERMIT: 14030331 |
| ADD: 1551 N FLAGLER # LPH 18 |
| CONT: CCSI USA, INC |
| TEL: (561)239-3665 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. MARCH 26/ 2014 |
| ACTION: BUILDING PROVISO |
| |
| 1) THE PLANS DO NOT INDICATE ANY REPLACEMENT OF |
| FLOORING ALTHOUGH WALLS ARE BEING MOVED AND REMOVED. |
| FOR REPLACEMENT FLOORING (TILE, MARBLE AND WOOD |
| FLOORING) THERE ARE CODE REQUIREMENTS THAT WILL NEED |
| ADDITIONAL INFORMATION PROVIDED: |
| |
| 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| 1B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING |
| FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF |
| NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| OF NOT MORE THAN 100. |
| |
| 1C) FBC-B 2010 603.2 EXCEPTION 2 WOOD FLOORS |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FBC-B 2010 |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |