2014-06-24 14:51:41 | RESIDENTIAL (R3) REVISION COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- PRODUCT APPROVAL INFORMATION SUBMITTED FOR CUSTOM |
| DOOR "A" NEED THE FOLLOWING INFORMATION FOR ROBERT |
| BROWN (BUILDING OFFICIAL) APPROVAL (PRODUCT APPROVAL |
| REQUIRED BY DCA RULE 9N-3): |
| A) WHERE WAS EXISTING DOOR TAKEN FROM?. PLANS DON'T |
| SHOW ANY DOOR TO BE REMOVED. |
| B) SIGNED AND SEALED COMPLETE ENGINEER DOOR COMPARATIVE |
| ANALYSIS. |
| C) ENGINEER TO REVISE THE DESIGN LOAD PER PERMITTED |
| DRAWINGS. -29.3 PSF DESIGN LOAD DOESN'T MATCH APPROVED |
| DRAWINGS. |
| D) ENGINEER TO PROVIDE COMPLETE INFORMATION FOR THE |
| HISTORIC DOOR. WOOD TYPE, THICKNESS, GLASS: TYPE, |
| THICKNESS, SIZES, ETC. |
| E) ENGINEER TO PROVIDE COMPLETE HISTORIC DOOR JAMB |
| SPECIFICATIONS AND ATTACHMENT TO THE STRUCTURE. |
| F) ENGINEER TO PROVIDE COMPLETE DOOR OPENING FRAMING |
| DETAILS AND SPECIFICATIONS. |
| |
| ***NOTE: ENGINEER TO CONTACT ROBERT BROWN (BUILDING |
| OFFICIAL) TO COORDINATE PRODUCT APPROVAL REQUIRED |
| INFORMATION. CALL (561)805-6652 OR E-MAIL |
| [email protected]. |
| |
| |
| 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS |
| TO FBC. (REPEAT COMMENT). |
| |
| 3- ENGINEER TO REVISE PLANS SHOWING: |
| A) SAFETY GLASS FOR WINDOW ADJACENT TO THE SPA. SEC. |
| R308.4(6). |
| ***NOTE: 3M SAFETY & SECURITY WINDOW FILM SPECS WERE |
| PROVIDED. ENGINEER TO REVISE PLANS SHOWING THE |
| INSTALLATION OF THIS 3M FILM AS THE PROPOSED MEANS OF |
| COMPLYIING WITH THE SAFETY GLASS REQUIREMENTS. |
| SEC. 104.11 CITY AMENDMENTS TO FBC (ALTERNATIVE |
| MATERIALS, DESIGN AND METHODS OF CONSTRUCTION AND |
| EQUIPMENT). |
| |
| B) SAFETY GLASS FOR WINDOW ADJACENT TO THE NEW STAIRWAY |
| (TOP AND BOTTOM). SEC. R308.4.(7) AND SEC. R308.4(8). |
| (***NOTE: SAME RESPONSE TO ITEM #3(A) ABOVE APPLIES). |
| |
| ***NOTE: PLEASE PROVIDE A RESPONSE LETTER ADDRESSING |
| EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |