2014-05-21 17:03:41 | RESIDENTIAL (R3) REVISION THIRD CHECKLIST. |
| CODE: 2010 FBC. |
| |
| 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| |
| A) PROPOSED CUSTOM DOOR "A" SPECIFIED ON PLANS. |
| (***NOTE: THE DOOR DOESN'T HAVE TO BE IMPACT BECAUSE OF |
| THE 25% EXCEPTION ON SEC. 606.4 OF 2010 FBC-EXISTING |
| BUILDING. ****NOTE***** GLAZING IN DOOR NEEDS TO COMPLY |
| WITH THE SAFETY GLASS REQUIRED BY HAZARDOUS LOCATION |
| SEC. R308.4(1). A PRODUCT APPROVAL IS STILL REQUIRED |
| FOR ALL NEW DOORS. HISTORIC DOESN'T WAIVE THIS |
| REQUIREMENT). |
| |
| *******RESPONSE TO INFORMATION SUBMITTED: |
| (A) NO DOOR PRODUCT APPROVAL WAS SUBMITTED. ONLY |
| INFORMATION FOR HURRICANE SHUTTERS WAS SUBMITTED. |
| |
| (B) PROVIDE FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA |
| FOR THE HURRICANE SHUTTERS TO BE USED AS REQUIRED BY |
| DCA RULE 9N-3. INFORMATION SUBMITTED IS NOT AN APPROVED |
| PRODUCT APPROVAL. IF THERE IS NOT AN APPROVED FLORIDA |
| OR MIAMI-DADE PRODUCT APPROVAL, THEN MANUFACTURER MAY |
| APPLY FOR LOCAL PRODUCT APPROVAL. ( NOTE: SHUTTERS ARE |
| NOT REQUIRED. SEE ITEM 1(A) ABOVE). |
| |
| 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS |
| TO FBC. (REPEAT COMMENT). |
| |
| 3- FLAT ROOF ASSEMBLY: RAS 117 CALCULATIONS SUBMITTED |
| NEED THE ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS |
| REQUIRED BY CHAPTER 471 FLORIDA STATUTE WHEN SUBMITTING |
| INFORMATION FOR PUBLIC RECORDS. COPIES ARE NOT ALLOWED. |
| |
| 4- A)SPECIFY SAFETY GLASS FOR WINDOW ADJACENT TO THE |
| SPA. SEC. R308.4(6). |
| (***NOTE: HISTORIC DOESN'T WAIVE LIFE SAFETY ISSUES. |
| THE LIFE SAFETY CONDITION WAS CREATED BY THE NEW |
| ADDITION. PLEASE REVIEW SEC. 1104 AND SEC. 1105 OF THE |
| 2010 FBC-EXISTING BUILDING TO ADDRESS THE NEW LIFE |
| SAFETY ISSUES). |
| |
| B) SPECIFY SAFETY GLASS FOR WINDOW ADJACENT TO THE NEW |
| STAIRWAY (TOP AND BOTTOM). SEC. R308.4.(7) AND SEC. |
| R308.4(8). |
| (***NOTE: SAME RESPONSE TO ITEM #4(A) ABOVE APPLIES). |
| |
| *******RESPONSE TO INFORMATION SUBMITTED: |
| (A) 3M SAFETY FILM INFORMATION SUBMITTED: NEED TO |
| PROVIDE PROOF THAT FILM WAS TESTED IN ACCORDANCE WITH |
| CPSC 16 CFR 1201 AS REQUIRED BY SEC. R308.3.1 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| ***IMPORTANT: PLEASE CONFIRM WITH HISTORIC IF 3M SAFETY |
| FILM IS ALLOWED. |
| |
| |
| |
| *******************NEW COMMENT: |
| |
| 1- PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION |
| SCHEDULE. YOU MAY USE THE CITY SAMPLE OR PROVIDE ALL |
| THE INFORMATION ON A DIFFERENT FORMAT AS LONG AS ALL |
| THE REQUIRED INFORMATION IS PROVIDED. NEED THIS |
| INFORMATION TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OS SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| (SHUTTERS ARE NOT REQUIRED. SEE ITEM 1(A) ABOVE. |
| |
| |
| ***NOTE: PLEASE PROVIDE A RESPONSE LETTER ADDRESSING |
| EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |