2014-04-30 15:58:08 | RESIDENTIAL (R3) REVISION SECOND CHECKLIST. |
| CODE: 2010 FBC. |
| |
| 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) PROPOSED CUSTOM DOOR "A" SPECIFIED ON PLANS. |
| (***NOTE: THE DOOR DOESN'T HAVE TO BE IMPACT BECAUSE OF |
| THE 25% EXCEPTION ON SEC. 606.4 OF 2010 FBC-EXISTING |
| BUILDING. A PRODUCT APPROVAL IS STILL REQUIRED FOR ALL |
| NEW DOORS. HISTORIC DOESN'T WAIVE THIS REQUIREMENT). |
| |
| B) SIMPSON CONNECTOR A4 SPECIFIED ON ANCHOR SCHEDULE. |
| FLORIDA PRODUCT APPROVAL FL 5550 IS NOT LISTED ON THE |
| FLORIDA PRODUCT APPROVAL WEBSITE FOR THE 2010 CODE. |
| |
| 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS |
| TO FBC. |
| (***NOTE: ONLY THE FLAT ROOF NOA 13-0529.14 SUBMITTED |
| WAS REVIEWED BY THE ENGINEER). |
| |
| 3- FLAT ROOF INFORMATION SUBMITTED: |
| PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2 |
| COPIES) AS REQUIRED BY GENERAL LIMITATION #7 ON PAGE 19 |
| AND PAGE 27 OF NOA 13-0529.14 SUBMITTED. NEED THE |
| CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC. |
| R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. |
| |
| 4- A)SPECIFY SAFETY GLASS FOR WINDOW ADJACENT TO THE |
| SPA. SEC. R308.4(6). |
| (***NOTE: HISTORIC DOESN'T WAIVE LIFE SAFETY ISSUES. |
| THE LIFE SAFETY CONDITION WAS CREATED BY THE NEW |
| ADDITION. PLEASE REVIEW SEC. 1104 AND SEC. 1105 OF THE |
| 2010 FBC-EXISTING BUILDING TO ADDRESS THE NEW LIFE |
| SAFETY ISSUES). |
| |
| B) SPECIFY SAFETY GLASS FOR WINDOWS ADJACENT TO THE NEW |
| STAIRWAY (TOP AND BOTTOM). SEC. R308.4.(7) AND SEC. |
| R308.4(8). |
| (***NOTE: SAME RESPONSE TO ITEM #4(A) ABOVE APPLIES). |
| |
| |
| ***NOTE: PLEASE PROVIDE A RESPONSE LETTER ADDRESSING |
| EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |