2014-03-20 16:09:59 | REVISION, BUILDING REVIEW COMMENTS. |
| CODE; 2010 FBC. |
| |
| 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) PROPOSED CUSTOM/IMPACT DOOR "A" SPECIFIED ON PLANS. |
| |
| B) PROPOSED CAST-CRETE 8F8-1B BEAM AS SHOWN ON |
| FOUNDATION PLAN. |
| |
| C) FLAT ROOF. |
| ***NOTE: CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS |
| GOING TO BE INSTALLED. AND, PROVIDE SIGNED AND SEALED |
| RAS 117 CALCULATIONS IF THE APPROVED ASSEMBLY DOESN'T |
| MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| D) SIMPSON CONNECTOR A4 SPECIFIED ON ANCHOR SCHEDULE. |
| FLORIDA PRODUCT APPROVAL FL11506 IS NOT LISTED ON THE |
| FLORIDA PRODUCT APPROVAL WEBSITE FOR THE 2010 CODE. |
| |
| 2- ENGINEER TO REVIEW AND APPROVE IN WRITING (NOT |
| SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| |
| 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| INSTALLATION OF THE SCREEN ENCLOSURE. OR PROVIDE |
| COMPLETE INFORMATION UNDER A SEPARATE PERMIT. SEC. |
| 107.3.5.3 CITY AMENDMENTS. |
| |
| 4- A) SPECIFY SIZES OF THE ROOF DRAIN SCUPPERS AND |
| DOWNSPOUTS. SEC. R903.4. |
| |
| B) SPECIFY OVERFLOW DRAINS AND SCUPPERS SIZE AND |
| LOCATION AS REQUIRED BY SEC. R903.4.1. |
| |
| 5- SPECIFY HOW THE WATER FROM THE NEW ROOF IS GOING TO |
| BE CONTROLLED SO IT DOESN'T GO TO THE NEIGHBOR'S |
| PROPERTY. SEC. R401.3. THE WATER CAN'T BE DIVERTED TO |
| THE NEIGHBORS PROPERTY. |
| |
| 6- SPECIFY ROOF SLOPE. SEC. R905.11. |
| |
| 7- PROVIDE HANDRAILS AS REQUIRED BY SEC. R311.7.7. |
| |
| 8- A)SPECIFY SAFETY GLASS FOR WINDOW ADJACENT TO THE |
| SPA. SEC. R308.4(6). |
| |
| B) SPECIFY SAFETY GLASS FOR WINDOW ADJACENT TO THE NEW |
| STAIRWAY (TOP AND BOTTOM). SEC. R308.4.(7) AND SEC. |
| R308.4(8). |
| |
| 9- SPECIFY NEW PORCH ROOF CROSS VENTILATION. SEC. R806. |
| |
| 10- A) CLARIFY WHERE IS SECTION 2/S-1 TAKEN AT?. AND B) |
| REMOVE STAIRS ON EAST SIDE IF THEY ARE NOT GOING TO BE |
| BUILT. DON'T CROSS OUT BY PEN. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 11- SHEET S-2: |
| A) REVISE/CLARIFY INSTALLATION OF SIMPSON CONNECTOR A9 |
| (SIMPSON SP6) SPECIFIED ON SECTION 1/S-2. THIS IS AN |
| STUD TO PLATE CONNECTOR, NOT JOIST CONNECTOR. OR |
| PROVIDE COMPLETE ENGINEERING ANALYSIS SHOWING HOW THIS |
| CONNECTOR WILL WORK AS PROPOSED. SEC. 107.2.1.3 CITY |
| AMENDMENTS. |
| |
| B) SPECIFY HOW LONG ARE THE 1/2" J-BOLTS SPECIFIED ON |
| SECTION 1/S-2 TO FASTEN THE 2X8 P.T. SILL TO THE 8" |
| GROUT FILLED BOND BEAM OF THE STEM WALL. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| C) SPECIFY CONNECTORS AT THE ENDS OF 3-PLY VERSALAM LVL |
| BEAMS SHOWN ON PLANS AT ALL THREE EXTERIOR WALLS AND |
| THE INTERIOR BEAM HOLDING THE ROOF JOISTS. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| D) SPECIFY FINISH FLOOR DECKING AND FINISH CEILING AND |
| FASTENING. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 12- SHEET S-3: |
| A) REVISE EXPOSURE . BUILDING EXPOSURE IS "C" NOT "B". |
| SEC. R301.2.1.4.3 |
| |
| B) REVISE DESIGN PRESSURES FOR ALL ROOF ZONES. ALSO, |
| REVISE THE DOORS/WINDOWS DESIGN PRESSURES. SEC. |
| R301.2.1.4.3. |
| |
| C) REVISE EXISTING BUILDING CODE NOTE: THIS IS NOT |
| ALTERATION LEVEL 2. THIS IS AN ADDITION. SEC. 407 OF |
| 2010 FBC-EXISTING BUILDING. |
| |
| |
| ***NOTE: PLEASE PROVIDE A RESPONSE LETTER ADDRESSING |
| EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |