Plan Review Notes For Permit 14030291 |
Permit Number |
14030291 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-03-27 15:10:04 | 5731 PREMIER PARK DRIVE | | PERMIT #14030291 | | MASTER #13120825 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PER NFPA 13, A CURRENT (WITHIN 12-MONTHS) WATER FLOW | | TEST IS REQUIRED. | | | | SUBMIT PRODUCT CUT-SHEETS FOR RISER EQUIPMENT AND | | SPRINKLERS TO BE INSTALLED. | | | | A HYDRAULIC SAFETY FACTOR OF 0.973 PSI IS INSUFFICIENT. | | DAILY FLUCTUATIONS IN THE WATER PRESSURE MAY RESULT IN | | A SPRINKLER SYSTEM THAT IS PRESSURE DEFICIENT TO | | OPERATE PROPERLY. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | | | | | | | |
|