 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 13, A CURRENT (WITHIN 12-MONTHS) WATER FLOW
 TEST IS REQUIRED.
  
 SUBMIT PRODUCT CUT-SHEETS FOR RISER EQUIPMENT AND
 SPRINKLERS TO BE INSTALLED.
  
 A HYDRAULIC SAFETY FACTOR OF 0.973 PSI IS INSUFFICIENT.
 DAILY FLUCTUATIONS IN THE WATER PRESSURE MAY RESULT IN
 A SPRINKLER SYSTEM THAT IS PRESSURE DEFICIENT TO
 OPERATE PROPERLY.
  