2014-03-25 06:33:29 | BUILDING PLAN REVIEW |
| REVISION: 14030258 |
| PERMIT: 14010760 |
| ADD: 1741 PALM BEACH LAKES # E224 |
| CONT: ANDERSON MOORE |
| TEL: (561) 401-1349/ LEXI |
| |
| 1ST REVIEW |
| DATE: TUESDAY/ MARCH 25/ 2014 |
| ACTION: DENIED |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1) THE PLANS SHOW ADDITIONAL WORK, AN INCREASE FROM THE |
| ORIGINAL SCOPE OF WORK COVERED UNDER THIS PERMIT AND |
| THE REVISION FORM STATES NO INCREASE IN VALUE. W P B |
| ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON |
| BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND |
| PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A |
| FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) THE LS1 SHEET SHOWS NEW WALLS BEING ADDED AND YET |
| THE PLANS INDICATE THE COMMON PATH OF TRAVEL THROUGH |
| THE WALL, NOT REFLECTING THE TRUE COMMON PATH OF |
| TRAVEL. 2010 FBC-B 1014.3. |
| |
| 3) SHEET A100 THE ACCESSIBLE DRESSING ROOM INDICATES |
| THE SIZE OF THE BENCH TO BE 3'-6" X 1'-0", H= 17". |
| PLEASE REFER TO THE 2010 FL ACCESSIBILITY CODE SECTION |
| 903.3 SIZE. |
| BENCHES SHALL HAVE SEATS THAT ARE 42 INCHES (1065 MM) |
| LONG MINIMUM AND 20 INCHES (510 MM) DEEP MINIMUM AND 24 |
| INCHES (610 MM) DEEP MAXIMUM. |
| |
| 4A) SHEET A100 THE ACCESSIBLE DRESSING ROOM BENCH DOES |
| NOT INDICATE HOW COMPLIANCE WITH SECTION 903.4 WILL BE |
| ACHIEVED. 903.4 BACK SUPPORT. |
| THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE |
| AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES |
| (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2 |
| INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A |
| POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT |
| SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM) |
| MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED |
| HORIZONTALLY. |
| |
| 4B) 903.6 STRUCTURAL STRENGTH. |
| ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS |
| USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS |
| (1112 N) IS APPLIED AT ANY POINT ON THE SEAT, FASTENER, |
| MOUNTING DEVICE, OR SUPPORTING STRUCTURE. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |