2014-03-07 13:35:41 | COMMERCIAL BUILDING, REROOF REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- PROVIDE FIELD WITHDRAWAL TEST (TAS 105) AS REQUIRED | | BY GENERAL LIMITATION #5 ON LAST PAGE OF NOA 13-0204.02 | | SUBMITTED. SEC. 1609 OF 2010 FBC. | | | | 2- ENGINEER TO PROVIDE RAS 117 CALCULATIONS USING THE | | FASTENER VALUE BASED ON THE RESULTS OF THE FIELD | | WITHDRAWAL TEST (TAS 105) AS REQUIRED BY ITEM #1 ABOVE. | | SEC. 1609 OF 2010 FBC. | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION WAS | | UPDATED TO $81,090 AS REQUIRED BY SEC. 109.3 OF CITY | | AMENDMENTS TO FBC. THE PERMIT FEE BALANCE IS $1971.72. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | | | |
|