Plan Review Notes
Plan Review Notes For Permit 14030208
Permit Number 14030208
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-03-14 16:30:198151 OKEECHOBEE BOULEVARD
 PERMIT #14030208
 MASTER #13121076
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET FP-1: GENERAL NOTE #2 INDICATES A HYDRAULIC AREA
 OF 1500 SQUARE FEET; HOWEVER, MULTIPLE HYDRAULIC AREAS
 APPEAR TO BE LESS THAN 1500 SQ.FT. IF UTILIZING THE
 AREA-REDUCTION METHOD FOR QUICK RESPONSE SPRINKLERS
 PLEASE INDICATE.
  
 SHEET FP-2: PER THE ENGINEER OF RECORD'S DRAWINGS, THE
 STORAGE AND ART LABS SHOULD BE DESIGNED AS ORDINARY
 HAZARD. ALSO, THE EXTENDED COVERAGE SPRINKLERS
 SUBMITTED ARE NOT LISTED FOR ORDINARY HAZARD
 PROTECTION.
  
 SHEET FP-2: SEVERAL OF THE BRANCH LINE CONFIGURATIONS
 ARE NOT SUPPORTED BY THE HYDRAULIC CALCULATIONS SUCH AS
 THE TREE SYSTEM PROTECTING THE COVERED WALKWAY, OR THE
 STANDARD RESPONSE SPRINKLERS LOCATED IN THE KITCHEN, OR
 THE TREE/GRID COMBINATION IN STORAGE #143.
  
 SHEET FP-3: PER THE ENGINEER OF RECORD'S DRAWINGS, THE
 SCIENCE LABORATORIES, STORAGE, AND ART LABS SHOULD BE
 DESIGNED AS ORDINARY HAZARD. ALSO, THE EXTENDED
 COVERAGE SPRINKLERS SUBMITTED ARE NOT LISTED FOR
 ORDINARY HAZARD PROTECTION.
  
 SHEET FP-3: THE THREE SPRINKLERS LOCATED AT THE TOP OF
 THE CENTER STAIR SHALL BE SUPPLIED BY THE FIRST FLOOR
 SPRINKLER SYSTEM AS THIS HIGH-CEILING IS PART OF THE
 FIRST FLOOR.
  
 SHEET FP-3: NO HIGH-TEMPERATURE SPRINKLER PROTECTION
 PROVIDED IN ROOM #210A FOR KILN.
  
 SHEET FP-3: NO HYDRAULIC CALCULATIONS SUBMITTED FOR THE
 SECOND FLOOR EXTENDED COVERAGE SPRINKLERS.
  
 GENERAL: NONE OF THE HYDRAULIC CALCULATIONS APPEAR TO
 BE ACCOUNTING FOR THE ADDITIONAL FRICTION LOSS
 ASSOCIATED WITH THE FLEXIBLE SPRINKLER DROPS. WHERE
 WILL THESE DROPS BE USED? EVERYWHERE?
  
 GENERAL: PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES
 FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 GENERAL: PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved