Plan Review Notes
Plan Review Notes For Permit 14030190
Permit Number 14030190
Review Stop M
Sequence Number 1
Notes
Date Text
2014-03-13 09:39:242010 FBC
  
 DENIED BY MECHANICAL
  
 1) NO MECHANICAL PLANS WERE SUBMITTED. A NEW MINI-SPLIT
 A/C IS SHOWN ON THE ELECTRICAL PLANS. A DRYER VENT AND
 BATHROOM EXHAUSTS ARE SHOWN ON THE PLANS. A MECHANICAL
 PERMIT IS REQUIRED. CITY AMENDMENTS 105.1
  
 2) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS
 FOR THE NEW MINI-SPLIT THAT WILL BE INSTALLED IN THE
 SUN ROOM. FBCR M1401.3
  
  
 3) SUBMIT TWO COPIES OF THE ARI SHEET FOR THE
 MINI-SPLIT. CITY AMENDMENTS 107.2.1.3
  
 4) PROVIDE DISCONNECTS FOR THE MINI-SPLIT CONDENSING
 UNIT AND AIR HANDLER AS REQUIRED BY THE 2008 NEC
 440.11.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]