Plan Review Notes For Permit 14030190 |
Permit Number |
14030190 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-03-13 09:39:24 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) NO MECHANICAL PLANS WERE SUBMITTED. A NEW MINI-SPLIT | | A/C IS SHOWN ON THE ELECTRICAL PLANS. A DRYER VENT AND | | BATHROOM EXHAUSTS ARE SHOWN ON THE PLANS. A MECHANICAL | | PERMIT IS REQUIRED. CITY AMENDMENTS 105.1 | | | | 2) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS | | FOR THE NEW MINI-SPLIT THAT WILL BE INSTALLED IN THE | | SUN ROOM. FBCR M1401.3 | | | | | | 3) SUBMIT TWO COPIES OF THE ARI SHEET FOR THE | | MINI-SPLIT. CITY AMENDMENTS 107.2.1.3 | | | | 4) PROVIDE DISCONNECTS FOR THE MINI-SPLIT CONDENSING | | UNIT AND AIR HANDLER AS REQUIRED BY THE 2008 NEC | | 440.11. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|