Plan Review Notes
Plan Review Notes For Permit 14030171
Permit Number 14030171
Review Stop M
Sequence Number 1
Notes
Date Text
2014-03-28 13:32:54AUDIT #: 1ST
 ACTION: DENIED
  
 FBC 2010 W/ 2012 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THIS IS AN AUDIT OF A PLAN SUBMITTED FOR PERMIT UNDER
 THE PROVISIONS OF FS 553.791. PLEASE ADDRESS THE
 FOLLOWING COMMENTS AND RESUBMIT:
  
 1. NO INFORMATION WAS PROVIDED REGARDING VENTILATION
 FOR THE NEWLY RECONFIGURED SPACES. PROVIDE VENTILATION
 CALCULATIONS WITH OCCUPANT LOADS BASED ON THE OCCUPANCY
 TYPES FOUND IN FBC-M TABLE 403.3 IN ACCORDANCE WITH
 FBC-EB 909.1.
  
 2. PAGE A-4 SHOWS THE RETURN AIR GRILL FOR AHU-1 BEING
 MOVED. THERE IS NOTHING ON THE PLANS SHOWING HOW
 BALANCED RETURN AIR IS TO BE ACHIEVED IN THE CONFERENCE
 ROOM. PROVIDE BALANCED RETURN PER FBC-M 601.4.
  