2014-03-28 13:32:54 | AUDIT #: 1ST | | ACTION: DENIED | | | | FBC 2010 W/ 2012 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | THIS IS AN AUDIT OF A PLAN SUBMITTED FOR PERMIT UNDER | | THE PROVISIONS OF FS 553.791. PLEASE ADDRESS THE | | FOLLOWING COMMENTS AND RESUBMIT: | | | | 1. NO INFORMATION WAS PROVIDED REGARDING VENTILATION | | FOR THE NEWLY RECONFIGURED SPACES. PROVIDE VENTILATION | | CALCULATIONS WITH OCCUPANT LOADS BASED ON THE OCCUPANCY | | TYPES FOUND IN FBC-M TABLE 403.3 IN ACCORDANCE WITH | | FBC-EB 909.1. | | | | 2. PAGE A-4 SHOWS THE RETURN AIR GRILL FOR AHU-1 BEING | | MOVED. THERE IS NOTHING ON THE PLANS SHOWING HOW | | BALANCED RETURN AIR IS TO BE ACHIEVED IN THE CONFERENCE | | ROOM. PROVIDE BALANCED RETURN PER FBC-M 601.4. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|