Plan Review Notes For Permit 14030155 |
Permit Number |
14030155 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-03-05 14:51:50 | APPROVED AS NOTED: | | IMPORTANT NOTICE: | | IN ADDITION TO THE REQUIREMENTS OF NEC ARTICLE 725 | | NEC 110.3(B) REQUIRES THAT THE TRANSFORMER BE SCREWED | | TO THE OUTLET | | NEC 112(A) REQUIRES THAT ALL UN-USED OPENINGS BE CLOSED | | NEC 110.22 REQUIRES THAT YOU MARK THE LOCATION OF THE | | TRANSFORMER | | NEC 110.26 REQUIRES A MINIMUM OF 3? CLEAR SPACE IN | | FRONT OF PANEL | | |
|