Plan Review Notes
Plan Review Notes For Permit 14030130
Permit Number 14030130
Review Stop P
Sequence Number 1
Notes
Date Text
2014-03-07 10:47:522010 FBC
  
 DENIED BY PLUMBING
  
 1) SPECIFY THE POOL PUMP THAT WILL BE USED ON THE
 PLANS. CITY AMENDMENTS 107.2.1 AND FBC R4101.6.3
  
  
 2) SUBMIT TWO COPIES OF THE SPECIFICATIONS AND THE PUMP
 CURVE DIAGRAM SHOWING THE MAXIMUM FLOW RATE IN GALLONS
 PER MINUTE FOR THE POOL PUMP. FBC R4101.6.3
  
 3) THE TDH CALCULATION THAT WAS ATTACHED TO THE PLAN
 INDICATES AN INTELLIFLO VS+SVRS. THE MAXIMUM FLOW RATE
 FOR THIS PUMP IS 145 GPM WITH A TDH OF 50'. THE WATER
 VELOCITY AT THIS FLOW RATE IN 2.5" PIPE IS MORE THAN
 THE 8 FT/SEC MAXIMUM ALLOWED FOR SUCTION PIPING. FBC
 R4101.6.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]