Plan Review Notes For Permit 14030111 |
Permit Number |
14030111 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-03-05 07:49:25 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE ONE STORY SINGLE FAMILY STRUCTURE IS LOCATED IN | | A 170 MPH VULT WIND SPEED AND EXPOSURE CATEGORY C. THE | | MAXIMUM DESIGN PRESSURES LISTED FOR THE ROOFING SYSTEM | | FASTENING OPTIONS ON PAGES 27 AND 28 OF NOA | | NO.13-0424.14 ARE NOT ADEQUATE FOR THE CORNER AND/OR | | PERIMETER AREAS OF THE FLAT ROOF. SPECIFY THE FASTENING | | OPTION THAT WILL BE USED AND SUBMIT TWO SETS OF SIGNED | | AND SEALED RAS 117 CALCULATIONS IN ACCORDANCE WITH | | GENERAL LIMITATION NUMBER 7 OF THE NOA. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|