Plan Review Notes For Permit 14030103 |
Permit Number |
14030103 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2014-04-07 09:12:54 | REROOF, THIRD BUILDING REVIEW CHECKLIST. | | CODE: 2010 FBC. | | | | 1- STEEL DECK: | | A) FLAT ROOF ASSEMBLY SELECTED ON THE RAS 117 | | CALCULATIONS SUBMITTED NOW DOESN'T MATCH ASSEMBLY SHOWN | | ON THE NOA 13-0424.13 SUBMITTED. REVISE AS REQUIRED TO | | MATCH. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | B) REVISE RAS 117 CALCULATIONS SUBMITTED. BASE SHEET | | FASTENING DOESN'T WORK FOR ROOF ZONES #2 AND #3 FOR THE | | CALCULATED DESIGN PRESSURES. SEC. 1609 FBC. | | | | 2- WOOD DECK: | | A)REVISE RAS 117 CALCULATIONS. BASE SHEET FASTENING | | DOESN'T WORK FOR ROOF ZONES # 2 AND #3 FOR THE | | CALCULATED DESIGN PRESSURES. SEC. 1609 FBC. REVISE AS | | REQUIRED. (REPEAT COMMENT. NOT ADDRESSED). | | | | ***NOTES: ANY ROOF EQUIPMENT REMOVAL OR RETROFIT ROOF | | DRAINS REQUIRE SEPARATE PERMITS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|