Plan Review Notes For Permit 14030103 |
Permit Number |
14030103 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-03-19 18:27:33 | REROOF BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- STEEL DECK: | | A) PROVIDE FASTENER WITHDRAWAL TEST (TAS 105) AS | | REQUIRED BY GENERAL LIMITATION #5 ON LAST PAGE OF NOA | | 13-0424.13 SUBMITTED. SEC. 1609 OF 2010 FBC. | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | REQUIRED BY GENERAL LIMITATION #7 ON PAGE 14 OF NOA | | 13-0424.13 SUBMITTED. | | | | 2- WOOD DECK: | | A) NOA 12-1003.05 SPECIFIED ON THE RAS 117 CALCULATIONS | | SUBMITTED DOESN'T MATCH THE NOA SUBMITTED. REVISE AS | | REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION WAS | | UPDATED TO $86,820. THE PERMIT FEE BALANCE IS $2175.54. | | | | ***NOTES: ANY ROOF EQUIPMENT REMOVAL OR RETROFIT ROOF | | DRAINS REQUIRE SEPARATE PERMITS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|