2014-09-30 11:54:47 | 705 NORTH OLIVE AVENUE |
| PERMIT #14030096 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| *****PROVISO - THE AMENITIES/LEASING OFFICE IS NOT |
| APPROVED FOR CONSTRUCTION AT THIS TIME UNTIL THE |
| FLOOR/CEILING OPENINGS DESIGN HAS BEEN RESOLVED***** |
| |
| ROUND #3 COMMENTS: |
| REPEAT COMMENT - SHEET A-0.1.2: SEVERAL AREAS IN THE |
| AMENITIES/LEASING OFFICE ARE OPEN TO THE FLOOR BELOW. |
| THE DESIGN SHALL CONFORM TO SECTION 8.6 VERTICAL |
| OPENINGS AS EITHER A COMMUNICATING SPACE, CONVENIENCE |
| OPENING, ATRIUM, OR MEZZANINE. FOR INSTANCE, EACH |
| OCCUPANT NOT IN THE COMMUNICATING SPACE (SUCH AS |
| AMENITY SECOND FLOOR REST ROOM) NEEDS TO HAVE ACCESS TO |
| AT LEAST ONE EXIT WITHOUT HAVING TO ENTER THE |
| COMMUNICATING SPACE, OR AS A CONVENIENCE OPENING, THE |
| OPENINGS NEED TO BE SEPARATED FROM CORRIDORS. |
| |
| REPEAT COMMENT - SHEET A-0.1: COULD NOT LOCATE INTERIOR |
| DESIGN SHEETS (ID SERIES) IN THIS SUBMITTAL. DRAWING |
| INDEX INDICATES A DOOR SCHEDULE ON SHEETS ID9.04 AND |
| ID9.05 WHICH COULD NOT BE FOUND. |
| |
| SHEET A-0.1.1: PROVIDE PANIC HARDWARE FOR POOL EXIT |
| ACCESS GATES AND FOR BUILDING EXIT DOORS SERVING POOL |
| OCCUPANTS. |
| |
| SHEET A-5.1.1. & A-5.1.7: PROVIDE A FIRE DOOR RATING |
| FOR VESTIBULE DOOR #CH112A |
| |
| SHEET A-2.1.7: PROVIDE SIGNAGE ON BOTH SIDES OF THE |
| DOOR #738.2 INDICATING "NOT AN EXIT." |
| |
| SHEETS A-0.1.4 & A-2.1.7: PROVIDE FIRE EXIT HARDWARE ON |
| DOORS #738.1 AND #756.1. DOOR #738.1 SERVES MORE THAN |
| 50 PERSONS AND SWINGS AGAINST THE FLOW OF EGRESS. |
| |
| SHEETS A-01.1. & E4.3 THE ARCHITECTURAL LIFE SAFETY |
| PLANS EXIT SIGNAGE AND THE ELECTRICAL PLANS EXIT |
| SIGNAGE NEED TO BE COORDINATED. |
| |
| NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101 |
| REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION |
| WITH FLORIDA AMENDMENTS.) |
| |