2014-09-09 15:25:58 | ***** THE PLUMBING HAS BEEN PASSED WITH THE FOLLOWING |
| PROVISOS: |
| WPB ADMIN. AMEND.TO 2010 FBC SEC.107.2.1. |
| 1) REVISED SANITARY RISER DRAWINGS SHALL BE SUBMITTED, |
| REVIEWED AND APPROVED BY THE BUILDING DIVISION PRIOR TO |
| THE FIRST PLUMBING INSPECTION BEING PERFORMED. |
| 2) RISER DRAWINGS SHALL BE SUBMITTED FOR THE PAN DRAIN |
| LINES, THE WATER HEATER TEMPERATURE & PRESSURE RELIEF |
| LINES, AND THE A/C CONDENSATE LINES WHEN THE REVISED |
| SANITARY RISER DRAWINGS ARE SUBMITTED. |
| **** THE FOLLOWING DEFICIENCIES OCCUR ON THE RISER |
| DRAWINGS: |
| 1) PLACE A NOTE ON DWG. 481-P-6.1 THAT THE LOCATION OF |
| VENTS FROM THE SANITARY DRAINAGE SYSTEM SHALL TERMINATE |
| IN ACCORDANCE WITH SEC.904.5 OF THE 2010 FLORIDA |
| PLUMBING CODE. IF POSSIBLE, SHOW THE LOCATION OF THE |
| VENT TERMINALS ON DWG.471 (P-2.1.9) |
| 2) THE GARAGE DRAINS AND THE TRENCH DRAINS ARE SHOWING |
| AS DRAINING "0" SQ. FT. CLARIFY. DWGS..480.2 & 480.3 ( |
| SHTS.P-5.5B & P-5.5C). |
| 3) DWG.#476- P-5.1 -THE WATER RISER FOR UNIT B1 APPEARS |
| TO HAVE THE PIPE SIZES REVERSED AND THE HOT AND COLD |
| WATER LINES ARE REVERSED ON THE LAYUOT AT SOME |
| FIXTURES. |
| 4) DWG.#477 - P-5.2 - PLEASE EXPLAIN HOW YOU ARRIVED AT |
| YOUR FIXTURE UNIT LOAD FOR THE WATER PIPING? IF YOU |
| USED APPENDIX "E" FROM THE FPC THAT IS AN ACCEPTED |
| METHOD. PLEASE REFERENCE SUCH ON THE PLAN. |
| 5) DWG.#578 - P-5.3 - THE SANITARY RISERS DO NOT |
| INCLUDE ALL THE FLOORS NOR THE FIXTURE LOAD OF EACH |
| FLOOR.SEE SPECIFIC RISER #'S |
| 1,4,81,18,29,22,25,92,93,94,95, & 98. CLARIFY. |
| 6) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE |
| DOMESTIC WATER PUMP. |
| 7) DWG. #479 IS LISTED AS P-5.4- THE SHEET PAGE IS |
| ACTUALLY P-5.4A AND SO IS DWG. # 479.1. THERE IS NO |
| SUCH SHT. P-5.4 NOR IS IT LISTED IN THE INDEX ON |
| DWG.#A-0.1. CLARIFY. |
| 8) DWG.# 479.2 - P-5.4B - RISER # 76 IS NOT SHOWN ON |
| THE SANITARY COLLECTION RISER SHEET. THERE ARE TWO |
| RISERS LABELED # 77. |
| 9) DWG.#479.2 - P-5.4B - RISER #82 SHOWS 10 F.U.'S ON |
| THIS STACK & DWG. #478 - P-5.3.SHOWS 35 F.U.'S. |
| 10) THE TYPICAL RISER PLAN SHOWS THE DIFFERENT RISRES |
| WITH A NOTE STATING " TO RISER.." THESE RISERS ARE NOT |
| VENTS THRU THE ROOF SO THIS IS CONFUSINF . PLEASE LIST |
| THE CONNECTING RISER/ CLARIFY. |
| 11) 479.3 - P-5.4C - SHOW THE SIZE OF RISERS # 84, 85, |
| 86. SHOW THE SIZE OF THE VENT STACK ON RISER # 89. |
| 12) 479.3 - RISER # 117 VENT STACK IS SHOWN AS 3" AND |
| ON 478 P-5.3 IT IS SHOWN AS 4". CLARIFY. |
| 13) 479.3- P-5.4C- SHOWS RISER #120 W/ A 2" VENT AND |
| 478 - P-5.3 SHOWS A 4" VENT.CLARIFY. |
| THIS IS NOT A COMPLETE LIST. |
| |
| |
| |