Plan Review Notes
Plan Review Notes For Permit 14030096
Permit Number 14030096
Review Stop P
Sequence Number 2
Notes
Date Text
2014-09-09 15:25:58***** THE PLUMBING HAS BEEN PASSED WITH THE FOLLOWING
 PROVISOS:
 WPB ADMIN. AMEND.TO 2010 FBC SEC.107.2.1.
 1) REVISED SANITARY RISER DRAWINGS SHALL BE SUBMITTED,
 REVIEWED AND APPROVED BY THE BUILDING DIVISION PRIOR TO
 THE FIRST PLUMBING INSPECTION BEING PERFORMED.
 2) RISER DRAWINGS SHALL BE SUBMITTED FOR THE PAN DRAIN
 LINES, THE WATER HEATER TEMPERATURE & PRESSURE RELIEF
 LINES, AND THE A/C CONDENSATE LINES WHEN THE REVISED
 SANITARY RISER DRAWINGS ARE SUBMITTED.
 **** THE FOLLOWING DEFICIENCIES OCCUR ON THE RISER
 DRAWINGS:
 1) PLACE A NOTE ON DWG. 481-P-6.1 THAT THE LOCATION OF
 VENTS FROM THE SANITARY DRAINAGE SYSTEM SHALL TERMINATE
 IN ACCORDANCE WITH SEC.904.5 OF THE 2010 FLORIDA
 PLUMBING CODE. IF POSSIBLE, SHOW THE LOCATION OF THE
 VENT TERMINALS ON DWG.471 (P-2.1.9)
 2) THE GARAGE DRAINS AND THE TRENCH DRAINS ARE SHOWING
 AS DRAINING "0" SQ. FT. CLARIFY. DWGS..480.2 & 480.3 (
 SHTS.P-5.5B & P-5.5C).
 3) DWG.#476- P-5.1 -THE WATER RISER FOR UNIT B1 APPEARS
 TO HAVE THE PIPE SIZES REVERSED AND THE HOT AND COLD
 WATER LINES ARE REVERSED ON THE LAYUOT AT SOME
 FIXTURES.
 4) DWG.#477 - P-5.2 - PLEASE EXPLAIN HOW YOU ARRIVED AT
 YOUR FIXTURE UNIT LOAD FOR THE WATER PIPING? IF YOU
 USED APPENDIX "E" FROM THE FPC THAT IS AN ACCEPTED
 METHOD. PLEASE REFERENCE SUCH ON THE PLAN.
 5) DWG.#578 - P-5.3 - THE SANITARY RISERS DO NOT
 INCLUDE ALL THE FLOORS NOR THE FIXTURE LOAD OF EACH
 FLOOR.SEE SPECIFIC RISER #'S
 1,4,81,18,29,22,25,92,93,94,95, & 98. CLARIFY.
 6) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 DOMESTIC WATER PUMP.
 7) DWG. #479 IS LISTED AS P-5.4- THE SHEET PAGE IS
 ACTUALLY P-5.4A AND SO IS DWG. # 479.1. THERE IS NO
 SUCH SHT. P-5.4 NOR IS IT LISTED IN THE INDEX ON
 DWG.#A-0.1. CLARIFY.
 8) DWG.# 479.2 - P-5.4B - RISER # 76 IS NOT SHOWN ON
 THE SANITARY COLLECTION RISER SHEET. THERE ARE TWO
 RISERS LABELED # 77.
 9) DWG.#479.2 - P-5.4B - RISER #82 SHOWS 10 F.U.'S ON
 THIS STACK & DWG. #478 - P-5.3.SHOWS 35 F.U.'S.
 10) THE TYPICAL RISER PLAN SHOWS THE DIFFERENT RISRES
 WITH A NOTE STATING " TO RISER.." THESE RISERS ARE NOT
 VENTS THRU THE ROOF SO THIS IS CONFUSINF . PLEASE LIST
 THE CONNECTING RISER/ CLARIFY.
 11) 479.3 - P-5.4C - SHOW THE SIZE OF RISERS # 84, 85,
 86. SHOW THE SIZE OF THE VENT STACK ON RISER # 89.
 12) 479.3 - RISER # 117 VENT STACK IS SHOWN AS 3" AND
 ON 478 P-5.3 IT IS SHOWN AS 4". CLARIFY.
 13) 479.3- P-5.4C- SHOWS RISER #120 W/ A 2" VENT AND
 478 - P-5.3 SHOWS A 4" VENT.CLARIFY.
 THIS IS NOT A COMPLETE LIST.
  
  
  