Plan Review Notes For Permit 14030096 |
Permit Number |
14030096 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-08-18 11:32:31 | PASS PROVISO | | | | 1) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S | | FLAM SPREAD OF NOT MORE THAN 25 AND SMOKE DEVELOPED | | INDEX NOT MORE THAN 50 OR UL 723 ( DRAIN LINES AND | | CLOSET DOORS) | | 2010 FBC (M) | | 2) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS ON | | THE | | CLOTHES DRYERS PER SECTION 504.6.4.1 SPECIFIED LENGTH | | 2010 FBC (M) | | 3) REFER TO SECTION 607.5.5 SHAFT ENCLOSURE. SMOKE | | FIRE DAMPERS ARE REQUIRED. 2010 FBC (M) | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|