Plan Review Notes For Permit 14030096
Permit Number 14030096
Review Stop M
Sequence Number 2
Notes
Date Text
2014-08-18 11:32:31PASS PROVISO
  
 1) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S
 FLAM SPREAD OF NOT MORE THAN 25 AND SMOKE DEVELOPED
 INDEX NOT MORE THAN 50 OR UL 723 ( DRAIN LINES AND
 CLOSET DOORS)
 2010 FBC (M)
 2) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS ON
 THE
 CLOTHES DRYERS PER SECTION 504.6.4.1 SPECIFIED LENGTH
 2010 FBC (M)
 3) REFER TO SECTION 607.5.5 SHAFT ENCLOSURE. SMOKE
 FIRE DAMPERS ARE REQUIRED. 2010 FBC (M)
  