 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 SHEET E-7.1.1; E-7.1.2
 PROVIDE MAIN BREAKERS FOR MC #3, MC # 6 AND MC# 7. NEC
 240.21
  
 SHEET E-6.1.1
 PROVIDE CLARIFICATION REGARDING THE SELECTION AND TYPE
 OF GROUND FAULT PROTECTION PROPOSED FOR THE SERVICE
 EQUIPMENT. NEC 230.95
  
 SHEET E-5.1.1; E-5.1.2; E-5.1.3; E-5.1.4
 VERIFY THAT ALL DOORS TO THE ELECTRICAL EQUIPMENT ROOMS
 ARE EQUIPPED WITH PANIC HARDWARE.
 NEC 110.26 C (3)
  
 SHEET E-5.1.2
 SUFFICIENT ACCESS AND WORKING SPACE HAS NOT BEEN
 PROVIDED FOR THE THIRD LEVEL METER ROOM. NEC 110.26
  
 SHEET E- 6.1.1
 THE ELECTRICAL POWER SOURCE FOR THE FIRE PUMP REQUIRES
 A SEPARATE AND RELIABLE POWER SOURCE. NEC 695.3
 CIRCUITS THAT SUPPLY ELECTRIC MOTOR-DRIVEN FIRE PUPS
 SHALL BE SUPERVISED FROM INADVERTENT DISCONNECTION. NEC
 695.4
 THE DISCONNECTION MEANS FOR THE FIRE PUMP SHALL NOT BE
 LOCATED WITHIN EQUIPMENT THAT FEEDS LOADS OTHER THAN
 THE FIRE PUMP. NEC 695.4
 VERIFY THE FIRE PUMP OVER CURRENT DEVICE WILL CARRY
 INDEFINITELY THE LOCKED-ROTOR CURRENT, THE CONDUCTORS
 HAVE A RATING OF NOT LESS THAN 125 PERCENT OF THE LOADS
 AND THE VOLTAGE DROP AT THE CONTROLLER IS WITHIN AN
 ACCEPTABLE RANGE. NEC 695.6, 695.7
 VERIFY THE FIRE PUMP CONDUCTORS ARE KEPT INDEPENDENT OF
 ALL OTHER WIRING AND ARE FIRE PROTECTED. NEC 695.6
 PROVIDE SPECIFICATIONS ON THE FIRE PUMP CONTROLLER. NEC
 695.4(B)(2), 90.7
 PROVIDE FIRE PUMP DISCONNECT AND CONTROLLER MARKINGS.
 NEC 695.4(B)(3) AND (4).
  
  