2014-05-03 11:29:37 | PLUMBING PLAN REVIEW |
| LOFTIN PLACE |
| PERMIT: 14030096 |
| ADD: 705 N OLIVE AVE |
| CONT: KAST CONSTRUCTION |
| TEL: (561)689-2910 |
| CONTACT: NEYITA (561)856-6655 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: SAT. MAY 03/2014 |
| ACTION: DENIED |
| |
| 632 DRAWING SHEETS ARE IN THIS ELECTRONIC SET OF PLANS |
| AND ARE LISTED 1-632. |
| |
| 1) MISSING PLUMBING SHEETS FROM THE INDEX AND THE |
| PLUMBING SHEETS THAT ARE FOUND IN THE FOUNDATION |
| PERMIT. |
| 1A) THE INDEX INDICATES SHEET P-1.1.1 SITE PLAN SHOULD |
| BE IN THIS SET OF DRAWINGS. ELECTRONIC SHEET 460. |
| |
| 1B) INDEX NOT SHOWING THESE SHEETS NOR THE ELECTRONIC |
| SHEETS MISSING NUMBERED 461, 462 & 463 ARE NOT FOUND IN |
| THIS SET. THIS IS A COMPLETE PLUMBING PLAN REVIEW OF |
| THE BUILDING TO FOLLOW THROUGH WITH THE MINIMUM |
| PLUMBING PLAN REVIEW FOR THE FOLLOWING SYSTEMS: |
| |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION107.3.5.1.3. PLUMBING |
| MINIMUM PLUMBING PLAN REVIEW: |
| SANITARY DRAINAGE MISSING PLUMBING FOUNDATION SHEETS |
| NOT COMPLETE |
| ROOF DRAINAGE MISSING PLUMBING FOUNDATION SHEETS |
| BACK FLOW PREVENTION 2010 FBC-PLUMBING 608.1. |
| IRRIGATION PLANS / BACKFLOW DEVICES/ RAIN SENSOR |
| CONTROLLERS F. S. 373.82 |
| LOCATION OF PLUMBING SUPPLY LINES 2010 FBC-PLUMBING |
| 603.2 CAN NOT BE VARIFIED |
| |
| 2) SHEET P-2.1.1A PARTIAL SHEET OF GROUND FLOOR NOT |
| INDEX GRID LINES MISSING TO IDENTIFY LOCATIONS. |
| |
| 2A) THIS SHEET ALSO INDICATES THE USE OF A SAND FILTER |
| IN THE 8 INCH GARAGE DRAIN LINE, PLEASE PROVIDE |
| ADDITIONAL INFORMATION TO THE LOCATION OF THE SAND |
| FILTER AND MANUFACTURERS SPECIFICATION. 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. PLANS INDICATE SEE |
| CIVIL DRAWINGS WHERE PLEASE? |
| |
| 2B) ROOMS ARE NOT IDENTIFIED, I BELIEVE THE 2 ROOMS |
| WITH 6 INCH FLOOR DRAINS ARE THE PUMP ROOM AND THE |
| TRASH COLLECTION/ TERMINATION ROOM A 4 INCH & THREE |
| INCH FLOOR DRAIN. THE FLOOR DRAIN SYSBOL IS NOT FOUND |
| ON THE PIPING SYMBOLS P-6.1 SHEET, IT IS HARD TO |
| DETERMINE IF THEY HAVE TRAPS OR NOT, BUT THEY DO NOT |
| INDICATE THE USE OF A TRAP PRIMER REQUIRED BY 2010 |
| FBC-P 1002.1 FIXTURE TRAPS. |
| |
| 2B)(1) THE DRAIN SCHEDULE FOUND ON P-6.1 DEALS WITH |
| TRAPS , ONE * (STAR) & ***THREE (STARS) DEAL WITH TRAPS |
| WITH MOVING PARTS (BALL-FLOAT ADOPTER) PLEASE REVIEW P- |
| 1002.3 PROHIBITED TRAPS. |
| THE FOLLOWING TYPES OF TRAPS ARE PROHIBITED: 1. TRAPS |
| THAT DEPEND ON MOVING PARTS TO MAINTAIN THE SEAL. |
| |
| 2B)(2) DEFINE A DEEP TRAP SEAL (SHOWN AS **** 4 STARS) |
| MECHANICAL EQUIPMENT AT ROOF. THIS TERM IS NOT IN THE |
| 2010 FBC-PLUMBING CODE. |
| M] 314.2.4 TRAPS. CONDENSATE DRAINS SHALL BE TRAPPED AS |
| REQUIRED BY THE EQUIPMENT OR APPLIANCE MANUFACTURER. |
| |
| 2C) THE 6 INCH SANITARY LOCATED IN THE N.E. PORTION OF |
| THE BILDING DOES NOT IDENTY THE TRANSITION TO 8 INCH |
| EXCEPT WHEN IT LEAVES THE BUILDING. 2010 FBC-P TABLE |
| 710.1(1) PROVIDE SLOPE PER FOOT DETERMINES DFU COUNT. |
| |
| 2D) THIS COMMENT IS FOR ALL FLOORS. PLEASE PLACE A PIPE |
| LEGEND ON EACH FLOOR LAYOUT SHEET AS TO WHAT CIRCLES,& |
| DIAMONDS REPRESENT, 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIED. REVIEWS CAN NOT BE COMPLETED AT THIS TIME |
| WITHOUT IDENTIFICATION. |
| |
| 3A) SHEET P-2.19 ROOF DECK AND THE TOP GARAGE PARKING |
| DECK DO NOT PROVIDE THE CALCULATIONS SHOWING |
| CONTRIBUTING PARAPET WALLS, THE |
| PLANS DO NOT PROVIDE AS TO WHAT RAINFALL THEIR DESIGN |
| IS FIGURED FOR UNDER THE 100 -YEAR HOURLY RAINFALL |
| BASED. SEE 2010 FBC-P SECTION 1106.1 AND FIGURE 1106.1. |
| |
| 3B) ROOF AND THE TOP GARAGE DECK TO PROVIDE IN THE |
| CALCULATIONS SQUARE FOOTAGE FOR VERTICAL WALLS IN |
| ACCORDANCE WITH THE 2010 FBC-PLUMBING 1106.4. |
| 1101.3 PROHIBITED DRAINAGE. |
| STORM WATER SHALL NOT BE DRAINED INTO SEWERS INTENDED |
| FOR SEWAGE ONLY. |
| 1101.4 TESTS. |
| THE CONDUCTORS AND THE BUILDING STORM DRAIN SHALL BE |
| TESTED IN ACCORDANCE WITH SECTION 312. |
| 1101.5 CHANGE IN SIZE. |
| THE SIZE OF A DRAINAGE PIPE SHALL NOT BE REDUCED IN THE |
| DIRECTION OF FLOW. |
| 1101.6 FITTINGS AND CONNECTIONS. |
| ALL CONNECTIONS AND CHANGES IN DIRECTION OF THE STORM |
| DRAINAGE SYSTEM SHALL BE MADE WITH APPROVED |
| DRAINAGE-TYPE FITTINGS IN ACCORDANCE WITH TABLE 706.3. |
| THE FITTINGS SHALL NOT OBSTRUCT OR RETARD FLOW IN THE |
| SYSTEM. |
| 1101.8 CLEANOUTS REQUIRED. |
| CLEANOUTS SHALL BE INSTALLED IN THE STORM DRAINAGE |
| SYSTEM AND SHALL COMPLY WITH THE PROVISIONS OF THIS |
| CODE FOR SANITARY DRAINAGE PIPE CLEANOUTS. |
| |
| 3C) IDENTIFY THE MATERIALS TO BE USED FOR THE |
| INSTALATION OF STORM WATER PIPING, SHOW COMPLIANCE |
| WITH: |
| 1102.1 GENERAL. |
| THE MATERIALS AND METHODS UTILIZED FOR THE CONSTRUCTION |
| AND INSTALLATION OF STORM DRAINAGE SYSTEMS SHALL COMPLY |
| WITH THIS SECTION AND THE APPLICABLE PROVISIONS OF |
| CHAPTER 7. |
| 1102.2 INSIDE STORM DRAINAGE CONDUCTORS. |
| INSIDE STORM DRAINAGE CONDUCTORS INSTALLED ABOVE GROUND |
| SHALL CONFORM TO ONE OF THE STANDARDS LISTED IN TABLE |
| 702.1. |
| 1102.3 UNDERGROUND BUILDING STORM DRAIN PIPE. |
| UNDERGROUND BUILDING STORM DRAIN PIPE SHALL CONFORM TO |
| ONE OF THE STANDARDS LISTED IN TABLE 702.2. |
| 1102.4 BUILDING STORM SEWER PIPE. |
| BUILDING STORM SEWER PIPE SHALL CONFORM TO ONE OF THE |
| STANDARDS LISTED IN TABLE 1102.4. |
| |
| 4) PLANS FAIL TO PROVIDE DETAILS FOR BOTH FL. |
| ACCESSIBILITY CODE PART A IF THERE ARE BUSINESS |
| OFFICES, RETAIL STORES, ETC AND PART II FAIR HOUSING |
| ACCESSIBILITY GUIDELINES. |
| |
| 2010 FBC-ACCESSIBILITY CODE 101.1.3 THIS CODE |
| ESTABLISHES STANDARDS FOR ACCESSIBILITY TO PLACES OF |
| PUBLIC ACCOMMODATION AND COMMERCIAL FACILITIES BY |
| INDIVIDUALS WITH DISABILITIES. THIS CODE SHALL ALSO |
| APPLY: TO STATE AND LOCAL GOVERNMENT FACILITIES |
| PURSUANT TO SECTION 553.503, F.S.; TO PRIVATE CLUBS |
| PURSUANT TO SECTION 553.505, F.S.; AND TO RESIDENTIAL |
| BUILDINGS PURSUANT TO SECTION 553.504(2), F.S., AND THE |
| ADA STANDARDS FOR ACCESSIBLE DESIGN. IT IS TO BE |
| APPLIED DURING THE DESIGN CONSTRUCTION AND ALTERATION |
| OF SUCH BUILDINGS AND FACILITIES AS REQUIRED BY THIS |
| CODE. |
| |
| FAIR HOUSING ACCESSIBILITY GUIDELINES SCOPE |
| THESE GUIDELINES APPLY ONLY TO THE DESIGN AND |
| CONSTRUCTION REQUIREMENTS OF 24 CFR 100.205. COMPLIANCE |
| WITH THESE GUIDELINES DO NOT RELIEVE PERSONS |
| PARTICIPATING IN A FEDERAL OR FEDERALLY-ASSISTED |
| PROGRAM OR ACTIVITY FROM OTHER REQUIREMENTS, SUCH AS |
| THOSE REQUIRED BY SECTION 504 OF THE REHABILITATION ACT |
| OF 1973 (29 U.S.C. 794) AND THE ARCHITECTURAL BARRIERS |
| ACT OF 1968 (42 U.S.C. 4151-4157). ACCESSIBLE DESIGN |
| REQUIREMENTS FOR SECTION 504 ARE FOUND AT CFR PART 8. |
| ACCESSIBLE DESIGN REQUIREMENTS FOR THE ARCHITECTURAL |
| BARRIERS ACT ARE FOUND AT 24 CFR PART 40. |
| PURPOSE |
| THE PURPOSE OF THESE GUIDELINES IS TO PROVIDE TECHNICAL |
| GUIDANCE ON DESIGNING DWELLING UNITS AS REQUIRED BY THE |
| FAIR HOUSING AMENDMENTS ACT OF 1988 (FAIR HOUSING ACT). |
| THESE GUIDELINES ARE NOT MANDATORY, NOR DO THEY |
| PRESCRIBE SPECIFIC REQUIREMENTS WHICH MUST BE MET, AND |
| WHICH, IF NOT MET, WOULD CONSTITUTE UNLAWFUL |
| DISCRIMINATION UNDER THE FAIR HOUSING ACT. BUILDERS AND |
| DEVELOPERS MAY CHOOSE TO DEPART FROM THESE GUIDELINES |
| AND SEEK ALTERNATE WAYS TO DEMONSTRATE THAT THEY HAVE |
| MET THE REQUIREMENTS OF THE FAIR HOUSING ACT. THESE |
| GUIDELINES ARE INTENDED TO PROVIDE A SAFE HARBOR FOR |
| COMPLIANCE WITH THE ACCESSIBILITY REQUIREMENTS OF THE |
| FAIR HOUSING ACT.SECTION 4. APPLICATION OF THE |
| GUIDELINES |
| REQUIREMENT 2. ACCESSIBLE AND USABLE PUBLIC AND COMMON |
| USE AREAS. |
| REQUIREMENT 6 - REINFORCED WALLS FOR GRAB BARS. |
| REQUIREMENT 7 - USABLE KITCHENS AND BATHROOMS. |
| |
| 5) NOTE NO ACTION NEEDS TO BE TAKEN, NOTICE! |
| SHEET P-6.1 THE PLUMBING FIXTURE CONNECTION SCHEDULE |
| PLEASE NOTE THE SHOWER IS LISTED WITH A 1 1/2 INCH TRAP |
| & 2 INCH WASTE THAT IS CODE COMMPLIANT WHEN USED WITH A |
| SHOWER BASED ON THE TOTAL FLOW RATE THROUGH SHOWER |
| HEADS AND BODY SPRAYS OF 5.7 GPM OR LESS. |
| |
| 6) SHEET P-6.1 DETAILS A TRASH CHUTE WITH A FLUSHING |
| SPRAY RING AT THE TOP OF THE ROOM OPERTED BY A SOLENOID |
| AND SWITCH IN THE TRASH ROOM. |
| PLEASE PROVIDE THE MANUFACTURERS SPEC ON THIS DEVICE, |
| LISTED FOR SUCH AN APPLICATION. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| PLEASE NOTE THIS DEVICE WILL NOT EXEMPT THE REQUIREMENT |
| FOR FIRE SPRINKLERS FOUND UNDER THE 2010 FBC-B |
| 903.11.2. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |