2014-04-30 09:34:24PLAN DENIED
 APARTMENTS
 1) PROVIDE DUCT SIZE GOING TO 36X6 GRILL
 2) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S
 2010 FBC (M)
 PROVIDE A DOOR SCHEDULE ON THE PLAN NEED TO KNOW WHAT
 TYPE OF
 DOOR IS GOING ON AIR HANDLER CLOSET, IF THE CLOSET IS A
 RETURN AIR
 PLENUM.
 3) REFER TO SECTION 501.2.2 EXHAUST OPENING PROTECTION
 2010 FBC (M)
  
 ROOF
 1) REFER TO SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 PROVIDE ENGINEER DETAIL ON A/C STANDS. HOW THE STANDS
 ARE
 TIED TO THE ROOF, AND HOW CONDENSERS ARE TIED TO THE
 STANDS.
 2) REFER TO SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 PROVIDE A DETAIL FROM THE ENGINEER FOR THE CURB TO ROOF
 TIE DOWN
 AND RTU TIE DOWN TO CURB.
 3) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS.
 FLORIDA ENERGY CODE 2010.
  
 LEASING OFFICE
 1) REFER TO SECTION 401.5 INTAKE OPENING PROTECTION.
 2010 FBC (M).
 2) REFER TO SECTION 501.2.2 EXHAUST OPENING PROTECTION
 2010 FBC (M)
 3) REFER TO SECTION 602.2.1 METERIALS WITHIN PLENUM'S.
 4) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 FLORIDA ENERGY CODE.
 5) REFER TO SECTION 601.4 BALANCED RETURN AIE 2010
 FBC (M)
 6) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEN.2010 FBC
 (M)
 7) REFER TO SECTION 606.3 INSTALLATION. 2010 FBC (M)
 8) REFER TO SECTION 606.4.1 SUPERVISION 2010 FBC (M)
 9) REFER TO SECTION 503.2.1 CALCULATION FOR HEATING AND
 COOLING
 LOADS. 2010 FLORIDA ENERGY CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  
  
  
  