Date |
Text |
2014-04-30 09:34:24 | PLAN DENIED |
| APARTMENTS |
| 1) PROVIDE DUCT SIZE GOING TO 36X6 GRILL |
| 2) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S |
| 2010 FBC (M) |
| PROVIDE A DOOR SCHEDULE ON THE PLAN NEED TO KNOW WHAT |
| TYPE OF |
| DOOR IS GOING ON AIR HANDLER CLOSET, IF THE CLOSET IS A |
| RETURN AIR |
| PLENUM. |
| 3) REFER TO SECTION 501.2.2 EXHAUST OPENING PROTECTION |
| 2010 FBC (M) |
| |
| ROOF |
| 1) REFER TO SECTION 301.12 WIND RESISTANCE 2010 FBC (M) |
| PROVIDE ENGINEER DETAIL ON A/C STANDS. HOW THE STANDS |
| ARE |
| TIED TO THE ROOF, AND HOW CONDENSERS ARE TIED TO THE |
| STANDS. |
| 2) REFER TO SECTION 301.12 WIND RESISTANCE 2010 FBC (M) |
| PROVIDE A DETAIL FROM THE ENGINEER FOR THE CURB TO ROOF |
| TIE DOWN |
| AND RTU TIE DOWN TO CURB. |
| 3) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS. |
| FLORIDA ENERGY CODE 2010. |
| |
| LEASING OFFICE |
| 1) REFER TO SECTION 401.5 INTAKE OPENING PROTECTION. |
| 2010 FBC (M). |
| 2) REFER TO SECTION 501.2.2 EXHAUST OPENING PROTECTION |
| 2010 FBC (M) |
| 3) REFER TO SECTION 602.2.1 METERIALS WITHIN PLENUM'S. |
| 4) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS |
| FLORIDA ENERGY CODE. |
| 5) REFER TO SECTION 601.4 BALANCED RETURN AIE 2010 |
| FBC (M) |
| 6) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEN.2010 FBC |
| (M) |
| 7) REFER TO SECTION 606.3 INSTALLATION. 2010 FBC (M) |
| 8) REFER TO SECTION 606.4.1 SUPERVISION 2010 FBC (M) |
| 9) REFER TO SECTION 503.2.1 CALCULATION FOR HEATING AND |
| COOLING |
| LOADS. 2010 FLORIDA ENERGY CODE. |
| |
| PLAN REVIEW BY HAROLD MOSER |
| [email protected] |
| OFFICE 561-805-6732 |
| FAX 561-805-6676 |
| |
| |
| |
| |
| |