Plan Review Notes
Plan Review Notes For Permit 14030046
Permit Number 14030046
Review Stop E
Sequence Number 1
Notes
Date Text
2014-03-24 12:54:17ADDITIONAL INFORMATION IS REQUIRED FOR THE ELECTRICAL
 SYSTEM. PLEASE PROVIDE A RISER DIAGRAM AND PANEL
 SCHEDULE INDICATING OVERCURRENT PROTECTION, PIPE AND
 WIRE SIZES FOR THE POOL AND ALL ASSOCIATED EQUIPMENT. A
 LOAD CALCULATION INDICATING THE TOTAL CONNECTED LOAD AT
 THE POOL PANEL AND A CALCULATION AT THE SERVICE
 EQUIPMENT INDICATING THE CAPACITY TO FEED THIS NEW LOAD
 FROM THE EXISTING SWITCHGEAR. PLEASE SHOW THE LOCATION
 AND ELEVATION OF NEW AND/OR EXISTING POWER AND LIGHTING
 WITH RESPECT TO THE INSIDE EDGE OF THE POOL AND HOW IT
 IS BEING FED.