Plan Review Notes
Plan Review Notes For Permit 14021097
Permit Number 14021097
Review Stop B
Sequence Number 5
Notes
Date Text
2015-01-05 08:39:492010 FBC
 4TH REVIEW
 DENIED BY BUILDING
  
 1) THE INFORMATION LISTED ON THE ENERGY CALCULATION IS
 NOT CONSISTANT WITH THE EQUIPMENT SIZING CALCULATIONS
 OR THE EQUIPMENT SCHEDULE ON THE MECHANICAL PLANS. THE
 SEER AND BTUS FOR THE HEATING AND COOLING ARE
 DIFFERENT. PLEASE CORRECT. THE INFORMATION ON THE PLANS
 AND ENERGY FORMS ARE REQUIRED TO BE CONSISTENT. FBC
 R107.2.1
 THE RESULTS ON THE RESUMBMITTED EQUIPMENT SIZING
 CALCULATIONS WERE IMPROPERLY CHANGED.
 THE EQUIPMENT SIZING CALCULATIONS CAN NOT BE CHANGED BY
 SOMEONE CROSSING OUT THE RESULTS ON THE SUMMARY SHEET
 AND WRITING IN DIFFERENT RESULTS. THE CARRIER MODEL
 24ACC624A HAS A MAXIMUM SEER OF 16 AND THE ENERGY
 CALCULATION FORM LISTS R-17. THE ENERGY CALCULATION
 FORM LISTS THE WALL INSULATION AS R-5 AND SHEET A102 OF
 THE PLANS HAS R-4.2THE EQUIPMENT SIZING CALCULATIONS
 AND THE ENERGY CALCULATIONS WILL NEED TO BE RE-DONE
 USING THE SAME INPUT INFORMATION SO THAT THE REPORTS
 ARE CONSISTENT WITH EACH OTHER.
  
 2) THE PREPARER AND THE OWNER/AGENT ARE REQUIRED TO
 SIGN THE ENERGY CALC. FORM. FBC ENERGY CONSERVATION
 SECTION 103.2.3.2 THE NEW FORMS ARE REQUIRED TO BE
 SIGNED.
  
 3) MAKE SURE THAT THE CORRECT INFORMATION APPEARS IN
 THE EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN. FBC
 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]