2014-10-30 11:41:10 | 2010 FBC |
| 2ND REVIEW |
| DENIED BY BUILDING |
| |
| 1) COMPLIED |
| |
| 2) COMPLIED |
| |
| 3) COMPLIED |
| |
| 4) COMPLIED |
| |
| 5) COMPLIED |
| |
| 6)COMPLIED |
| |
| 7) THE CITY AND PERMIT OFFICE ARE SPECIFIED AS RIVIERA |
| BEACH ON THE ENERGY CALCULATION. THIS PROJECT IS |
| LOCATED IN THE CITY OF WEST PALM BEACH (JURISDICTION |
| NUMBER 604700). PLEASE CORRECT. FBC ENERGY CONSERVATION |
| SECTION 103.2.1.1.1 |
| (THE ENERGY CALCULATIONS WILL NEED TO BE REDONE WITH |
| THE CORRECT INFORMATION.) |
| |
| 8) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY CALC. |
| FORM. FBC ENERGY CONSERVATION SECTION 103.2.3.2 |
| |
| 9) THE ATTIC DUCT INSULATION IS LISTED AS R-13 ON THE |
| ENERGY CALC. FORM AND THE MECHANICAL PLANS SPECIFY R-6. |
| PLEASE CORRECT. FBC ENERGY CONSERVATION SECTION |
| 103.2.3.2 ( THE INFORMATION ON THE PLANS AND ENERGY |
| FORMS ARE REQUIRED TO BE CONSISTENT. FBC R107.2.1 |
| |
| 10) THE ENERGY CALC. FORM SPECIFIES THAT THE EXTERIOR |
| CONCRETE BLOCK WALLS HAVE R-13 INSULATION. PROVIDE A |
| WALL SECTION THAT SHOWS THE TYPE OF INSULATION THAT |
| WILL BE INSTALLED. CITY AMENDMENTS 107.2.1 & FBC ENERGY |
| CONSERVATION SECTION 103.2.1.1.1 ( THE PLANS SPECIFY |
| R-4.2 INSULATION ON THE EXTERIOR CONCRETE WALLS. ) |
| |
| 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE PGT |
| & LAWSON SINGLE HUNG WINDOWS THAT ARE SPECIFIED ON PLAN |
| SHEET A102 AND FOR THE STRUCTURAL MULLIONS AS REQUIRED |
| BY DCA RULE 9N-3. MIAMI-DADE NOAS AND FLORIDA PRODUCT |
| APPROVALS ARE ACCEPTABLE. |
| |
| 12) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| THE PROJECT. CITY AMENDMENTS 107.3.4.1 |
| |
| 13) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR OPENING |
| PROTECTION FROM LARGE MISSILE IMPACT. IF STORM PANELS |
| ARE USED SUBMIT TWO COPIES OF THEIR PRODUCT APPROVALS, |
| AN INSTALLATION SCHEDULE AND A KEY PLAN. DCA RULE 9N-3 |
| & CITY AMENDMENTS 107.2.1. |
| |
| 14) IN ORDER TO SPEED PLAN REVIEW, PLEASE SUBMIT A |
| RESPONSE LETTER THAT INDICATES HOW EACH OF THE REVIEW |
| COMMENTS WAS ADDRESSED. |
| |