2014-07-16 15:47:33 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THIS |
| STRUCTURE IS LOCATED IN 17O MPH VULT WIND SPEED AND |
| EXPOSURE CATEGORY C. THE FBCR 301.2.1 |
| |
| 2) PROVIDE A STRUCTURAL DETAIL FOR THE CONCRETE BLOCK |
| WALL IN-FILL AT THE KITCHEN WINDOW THAT SHOWS THE |
| REINFORCING BAR SIZE AND LOCATION. CITY AMENDMENTS |
| 107.2.1.3 & FBCR 301.1 |
| |
| 3) THE TYPE OF CONSTRUCTION FOR THIS STRUCTURE IS V-B |
| PER FBC TABLE 601. PLEASE CORRECT BUILDING TYPE ON |
| SHEET A100. |
| |
| 4) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR SMOKE ALARMS |
| AND FBCR 315 FOR CARBON MONOXIDE ALARMS. |
| |
| 5) SHOW THAT THE BATHROOM WINDOWS COMPLY WITH FBCR |
| 308.4 FOR SAFETY GLAZING IN HAZARDOUS LOCATIONS. |
| |
| 6) THE WINDOW BUCK DETAIL ON SHEET A102 SPECIFIES 3/13" |
| X 1-3/4" TAPCONS WITH A 1-1/4" MINIMUM WOOD EMBED. THE |
| EXTERIOR WALLS ARE CONCRETE BLOCK NOT WOOD. THE LENGTH |
| OF THE TAPCONS WILL NOT PROVIDE AN 1-1/4" EMBED DEPTH |
| WHEN FASTENED THROUGH A 3/4" BUCK AND A 1/4" SHIM |
| SPACE. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 AND FBCR |
| 612.10.2.1 |
| |
| 7) THE CITY AND PERMIT OFFICE ARE SPECIFIED AS RIVIERA |
| BEACH ON THE ENERGY CALCULATION. THIS PROJECT IS |
| LOCATED IN THE CITY OF WEST PALM BEACH (JURISDICTION |
| NUMBER 604700). PLEASE CORRECT. FBC ENERGY CONSERVATION |
| SECTION 103.2.1.1.1 |
| |
| 8) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY CALC. |
| FORM. FBC ENERGY CONSERVATION SECTION 103.2.3.2 |
| |
| 9) THE ATTIC DUCT INSULATION IS LISTED AS R-13 ON THE |
| ENERGY CALC. FORM AND THE MECHANICAL PLANS SPECIFY R-6. |
| PLEASE CORRECT. FBC ENERGY CONSERVATION SECTION |
| 103.2.3.2 |
| |
| 10) THE ENERGY CALC. FORM SPECIFIES THAT THE EXTERIOR |
| CONCRETE BLOCK WALLS HAVE R-13 INSULATION. PROVIDE A |
| WALL SECTION THAT SHOWS THE TYPE OF INSULATION THAT |
| WILL BE INSTALLED. CITY AMENDMENTS 107.2.1 & FBC ENERGY |
| CONSERVATION SECTION 103.2.1.1.1 |
| |
| 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE PGT |
| & LAWSON SINGLE HUNG WINDOWS THAT ARE SPECIFIED ON PLAN |
| SHEET A102 AND FOR THE STRUCTURAL MULLIONS AS REQUIRED |
| BY DCA RULE 9N-3. MIAMI-DADE NOAS AND FLORIDA PRODUCT |
| APPROVALS ARE ACCEPTABLE. |
| |
| 12) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| THE PROJECT. CITY AMENDMENTS 107.3.4.1 |
| |
| 13) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR OPENING |
| PROTECTION FROM LARGE MISSILE IMPACT. IF STORM PANELS |
| ARE USED SUBMIT TWO COPIES OF THEIR PRODUCT APPROVALS, |
| AN INSTALLATION SCHEDULE AND A KEY PLAN. DCA RULE 9N-3 |
| & CITY AMENDMENTS 107.2.1. |
| |
| 14) IN ORDER TO SPEED PLAN REVIEW, PLEASE SUBMIT A |
| RESPONSE LETTER THAT INDICATES HOW EACH OF THE REVIEW |
| COMMENTS WAS ADDRESSED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |