Plan Review Notes
Plan Review Notes For Permit 14021097
Permit Number 14021097
Review Stop B
Sequence Number 2
Notes
Date Text
2014-07-16 15:47:332010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THIS
 STRUCTURE IS LOCATED IN 17O MPH VULT WIND SPEED AND
 EXPOSURE CATEGORY C. THE FBCR 301.2.1
  
 2) PROVIDE A STRUCTURAL DETAIL FOR THE CONCRETE BLOCK
 WALL IN-FILL AT THE KITCHEN WINDOW THAT SHOWS THE
 REINFORCING BAR SIZE AND LOCATION. CITY AMENDMENTS
 107.2.1.3 & FBCR 301.1
  
 3) THE TYPE OF CONSTRUCTION FOR THIS STRUCTURE IS V-B
 PER FBC TABLE 601. PLEASE CORRECT BUILDING TYPE ON
 SHEET A100.
  
 4) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR SMOKE ALARMS
 AND FBCR 315 FOR CARBON MONOXIDE ALARMS.
  
 5) SHOW THAT THE BATHROOM WINDOWS COMPLY WITH FBCR
 308.4 FOR SAFETY GLAZING IN HAZARDOUS LOCATIONS.
  
 6) THE WINDOW BUCK DETAIL ON SHEET A102 SPECIFIES 3/13"
 X 1-3/4" TAPCONS WITH A 1-1/4" MINIMUM WOOD EMBED. THE
 EXTERIOR WALLS ARE CONCRETE BLOCK NOT WOOD. THE LENGTH
 OF THE TAPCONS WILL NOT PROVIDE AN 1-1/4" EMBED DEPTH
 WHEN FASTENED THROUGH A 3/4" BUCK AND A 1/4" SHIM
 SPACE. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 AND FBCR
 612.10.2.1
  
 7) THE CITY AND PERMIT OFFICE ARE SPECIFIED AS RIVIERA
 BEACH ON THE ENERGY CALCULATION. THIS PROJECT IS
 LOCATED IN THE CITY OF WEST PALM BEACH (JURISDICTION
 NUMBER 604700). PLEASE CORRECT. FBC ENERGY CONSERVATION
 SECTION 103.2.1.1.1
  
 8) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY CALC.
 FORM. FBC ENERGY CONSERVATION SECTION 103.2.3.2
  
 9) THE ATTIC DUCT INSULATION IS LISTED AS R-13 ON THE
 ENERGY CALC. FORM AND THE MECHANICAL PLANS SPECIFY R-6.
 PLEASE CORRECT. FBC ENERGY CONSERVATION SECTION
 103.2.3.2
  
 10) THE ENERGY CALC. FORM SPECIFIES THAT THE EXTERIOR
 CONCRETE BLOCK WALLS HAVE R-13 INSULATION. PROVIDE A
 WALL SECTION THAT SHOWS THE TYPE OF INSULATION THAT
 WILL BE INSTALLED. CITY AMENDMENTS 107.2.1 & FBC ENERGY
 CONSERVATION SECTION 103.2.1.1.1
  
 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE PGT
 & LAWSON SINGLE HUNG WINDOWS THAT ARE SPECIFIED ON PLAN
 SHEET A102 AND FOR THE STRUCTURAL MULLIONS AS REQUIRED
 BY DCA RULE 9N-3. MIAMI-DADE NOAS AND FLORIDA PRODUCT
 APPROVALS ARE ACCEPTABLE.
  
 12) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.3.4.1
  
 13) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR OPENING
 PROTECTION FROM LARGE MISSILE IMPACT. IF STORM PANELS
 ARE USED SUBMIT TWO COPIES OF THEIR PRODUCT APPROVALS,
 AN INSTALLATION SCHEDULE AND A KEY PLAN. DCA RULE 9N-3
 & CITY AMENDMENTS 107.2.1.
  
 14) IN ORDER TO SPEED PLAN REVIEW, PLEASE SUBMIT A
 RESPONSE LETTER THAT INDICATES HOW EACH OF THE REVIEW
 COMMENTS WAS ADDRESSED.
  