2014-07-16 13:52:092010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN OF THE MECHANICAL SYSTEM IS
 REQUIRED ON THE PLANS. CITY AMENDMENTS 107.2.1
  
 2) SPECIFY THE SIZE OF THE RETURN AIR TRANSFER DUCTS TO
 SHOW COMPLIANCE WITH FBCR M 1602.4 FOR BALANCED RETURN
 AIR.
  
 3) SPECIFY THE SIZE OF THE SUPPLY DUCT TO THE NEW
 BATHROOM. CITY AMENDMENTS 107.3.5.3
  
 4) THE BATHROOM EXHAUST DUCTS ARE REQUIRED TO DISCHARGE
 DIRECTLY TO THE OUTDOORS. FBCR M1507.2
  
 5) INDICATE HOW THE RETURN AIR WILL GET TO THE AIR
 HANDLER THAT IS LOCATED IN THE CLOSET. IF IT IS THROUGH
 THE BI-FOLD DOORS, SPECIFY THAT THEY WILL BE LOUVERED.
 FBCR M1602
  