2014-02-27 16:48:032010 FBC
  
 DENIED BY BUILDING
  
 1) THE APPLICATION SPECIFIES THAT 1100 SQUARE FEET OF
 THE THE BUILDING IS BEING RE-ROOFED. THE BUILDING
 SKETCH THAT I DOWNLOADED FROM THE PROPERTY APPRAISER'S
 WEBSITE INDICATES THE MAIN HOUSE IS 1531 SQFT WHICH
 INCLUDES A SCREENED PORCH, AN ENCLOSED PORCH AND A
 CARPORT. THERE IS ALSO A DETACHED GARAGE OF 216 SQFT.
 PLEASE PROVIDE A SKETCH WITH DIMENSIONS SHOWING THE
 WHICH AREAS THAT WILL BE RE-ROOFED TO MAKE UP 1100
 SQFT. CITY AMENDMENTS 107.2.1 AND 107.2.1.3
  
 2) THE PERMIT APPLICATION SPECIFES THAT ROOF SYSTEM NO.
 W-33 WILL BE USED. ON THE PRODUCT APPROVAL THAT WAS
 SUBMITTED, THE W-33 SYSTEM IS CROSSED OUT AND THE W-32
 SYSTEM IS CHECKED. THE W-32 SUSTEM HAS A MAXIMUM DESIGN
 PRESSURE OF -75 PSF WHICH IS TOO LOW FOR THE CORNER
 AREAS FOR THIS PROJECT. PLEASE CLARIFY. CITY AMENDMENTS
 107.2.1.2
  
 3) PLEASE NOTE THAT THE BASE SHEET FASTENERS REQUIRED
 FOR BOTH SYSTEM NO. W-32 AND W-33 ARE DRILL-TEC SCREWS
 WITH METAL PLATES AS SPECIFIED IN NOTE 2 ON PAGE 2 OF
 60 FROM THE PRODUCT APPROVAL.
  