2014-03-03 17:04:45AS PER NEC THE INTERIOR OF AN UNDERGROUND (OR IN
 CONCRETE SLAB) RACEWAY SHALL BE CONSIDERED A WET
 LOCATION; ALL CONDUCTORS WITHIN THE RACEWAY SHALL BE
 LISTED ACCORDINGLY.
 ALL LOW VOLTAGE & CONTROL OR COMMUNICATION WIRING SHALL
 BE LISTED FOR THE APPLICATION