2014-04-22 08:15:02 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) THE TRUSS PLACEMENT PLAN AND TRUSS DRAWING COVER |
| SHEET THAT WERE SUBMITTED DO NOT HAVE THE ORIGINAL WET |
| SIGNATURE OF THE ENGINEER AS REQUIRED BY FAC |
| 61G15-23.002 FOR DOCUMENTS THAT ARE SUBMITTED FOR |
| PUBLIC RECORD. |
| |
| 2) THE TRUSS PLACEMENT PLAN IS TOO SMALL. CITY |
| AMENDMENT 107.2.1.4 TO THE FBC REQUIRES PLANS SUBMITTED |
| FOR RECORD TO BE A MINIMUM 1/8 INCH SCALE. |
| |
| 3) THE TRUSS PLACEMENT PLAN THAT WAS SUBMITTED IS FOR |
| THE ALTERNATE ROOF FRAMING PLAN. THERE ARE TWO |
| DIFFERENT ROOF FRAMING PLANS SPECIFIED ON SHEET S-1 OF |
| THE PLAN. THE FIRST ONE HAS A GABLE END AT THE BACK OF |
| THE STRUCTURE AND THE ALTERNATE ONE HAS A HIP ROOF AT |
| THE BACK. PLEASE SUBMIT BOTH TRUSS PACKAGES OR REVISE |
| THE PLANS TO REMOVE THE GABLE OPTION. CITY AMENDMENTS |
| 107.2.1 |
| |
| 4) THERE IS A DISCREPANCY BETWEEN THE STRUCTURAL ROOF |
| FRAMING PLAN AND THE TRUSS PLACEMENT PLAN AND TRUSS |
| DRAWINGS THAT WAS NOTED ON THE SHOP DRAWING REVIEW. THE |
| STRUCTURAL ROOF PLANS SHOW THE HIP AND JACK TRUSSES AT |
| THE FRONT BEARING ON THE FRONT WALL OF THE STRUCTURE |
| AND THE TRUSS PLACEMENT PLAN AND TRUSS DRAWINGS HAVE |
| THEM ATTACHED TO A HIP GIRDER TRUSS THAT WILL CARRY |
| THIER LOAD AND TRANSFER IT TO THE SIDE WALLS. THE TRUSS |
| ANCHORS SPECIFIED FOR THIS TRUSS ARE NOT ADEQUATE FOR |
| THIS ADDITIONAL LOADING. THIS WILL NEED TO BE CORRECTED |
| BEFORE THE MASTER PERMIT CAN BE APPROVED. CITY |
| AMENDMENTS 107.2.1 AND FBC R802.1.6.5 |
| |