Plan Review Notes
Plan Review Notes For Permit 14020917
Permit Number 14020917
Review Stop M
Sequence Number 1
Notes
Date Text
2014-03-26 14:28:28MECHANICAL PLAN REVIEW
 PERMIT: 14020917
 ADD: 1645 PALM BEACH LAKES #1000 & 1010
 CONT: FISHER CONTRACTING
 TEL: (561)691-4716
  
 1ST REVIEW
 DATE: WEDNESDAY MARCH 26/ 2014
 YEAR BUILT 1981
 ACTION: DENIED
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1) SHEET M2.1 DOES NOT INDICATE THE MEDIUM PRESSURE
 DUCT WORK NOR DOES THE PLANS SHOW THE VAV BOXES. THERE
 IS A NEW TENANT SEPERATION WALL SHOWN ON SHEET A2 WITH
 A DETAIL 1/ A3 TO BE A ONE HOUR FIRE RATED WALL. PLEASE
 SHOW COMPLIANCE WITH 2010 FBC-M 607.5.3 FIRE PARTITIONS
 & 607.4
 ACCESS & IDENTIFICATION.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]