2014-03-17 16:24:06THE FIRST ELECTRICAL REVIEW FAILED AND THE FOLLOWING
 DEFICIENCIES WERE NOTED:
 1. STATE/INDICATE. THE APPLICABLE CODE ON THE -PLANS
 (2008 EDITION OF THE NATIONAL ELECTRICAL CODE)
 2 PAGE NUMBERS AS SUBMITTED DO NOT MATCH THE DRAWING
 INDEX.
 3. ELECTRICAL NOTES 1 & ELECTRICAL SPECIFICATIONS 4
 CONFLICT WITH EACH OTHER.
 4. NEC HAS SPECIFIC OUTLET PLACEMENTS REQUIREMENTS ON
 SECTION 210.52 THAT SHALL BE OBSERVED.
 5. NEC 210.8 HAS SPECIFIC GFCI REQUIREMENTS WHICH HAVE
 TO BE FOLLOWED.
 6. NEC 210.12 HAS ARC-FAULT REQUIREMENTS
 7. NEC 406.11 ADDRESSES TAMPER-RESISTANT DEVICES
 8. SHALL SUBMIT PANEL SCHEDULES FOR BOTH, PANELS A & B
 9. INCLUDE THE COMPASS ARROW ON THE ELECTRICAL DRAWINGS
 10 THE LOCATION OF THE 5 CONDENSING UNITS SHALL BE
 INDICATED ON THE DRAWINGS.
  
 IT IS NOT THE INTENT OF THIS REVIEW TO PROVIDE A PUNCH
 LIST FOR YOUR DESIGN PROFESSIONAL, BUT IF THERE ARE ANY