Plan Review Notes For Permit 14020863 |
Permit Number |
14020863 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-04-09 12:43:10 | TODAY I MADE A SECOND ATTEMPT TO REACH DUANE MILLAR. | | LEFT VM AND ALSO TRIED DIALING 0. GOT VOICE MAIL AS | | WELL. RETURNED PLANS TO BIN WHILE WAITING FOR RESPONSE. | 2014-04-08 19:03:25 | ERRORS AND DISCREPANCIES WERE NOTED ON THE RISER | | DIAGRAM AND PANEL SCHEDULES. I CALLED DUANE AND LEFT A | | MESSAGE FOR A CALL BACK. | | | | COMMENTS 1 & 2 PROPERLY ADDRESSED MY PRIOR CONCERNS, | | BUT THERE IS AN ISSUE WITH #3. | | 1. THE RISER DIAGRAM DOES NOT REFLECT ANY NEW WORK AS | | IDENTIFIED BY THE LEGEND, YET THIS EQUIPMENT IS BEING | | RELOCATED. PREVIOUSLY I ASKED FOR CONDUCTOR SIZING AND | | IT WAS NOT PROVIDED. ACCORDING TO THE RISER DIAGRAM | | PANEL "HB" IS FED FROM A 400 AMP DISCONNECT. OUT OF | | PANEL "HB" VIA A 175 AMP OCPD IS FED A 112 KVA | | TRANSFORMER SERVING PANEL "LBA" W/A 400 AMP MAIN | | BREAKER AND A CONNECTED LOAD OF ONLY 70 AMP. | | | | WHAT ARE THE CONDUCTOR SIZES FOR THESE FEEDERS? | | | | 2. THE PANEL SCHEDULE FOR "HB" DOES NOT REFLECT THE | | OVER CURRENT DEVICE FOR THE TRANSFORMER AS INDICATED. |
|