2014-02-24 17:41:08THE FOLLOWING ITEMS ARE MISSING FROM THE SUBMITTED
 DRAWING FOR APPROVAL:
 1. INDICATE THE PROPOSED LOCATION OF THE SERVICE IN
 RELATION AND COMPLIANCE WITH THE NEC 682 DATUM
 ELECTRICAL PLANE.
 2. NEC 682.11 REQUIRES A SHUNT TRIP OR SIMILAR DEVICE
 TO SHUT DOWN THIS SERVICE SHOULD THE WATER RISE ABOVE
 THE ELECTRICAL DATUM PLANE.