Plan Review Notes
Plan Review Notes For Permit 14020820
Permit Number 14020820
Review Stop B
Sequence Number 1
Notes
Date Text
2014-03-05 11:24:34****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE PLAN, FBC 107.
  
 2. INCLUDE WIND DESIGN CRITERIA FBC 2010 RESIDENTIAL
 301.1.
  
 3. INCLUDE METHOD OF DESIGN FBC 2010 RESIDENTIAL
 301.2.1.1.
  
 4. PLANS TO BE ARCHITECTURAL QUALITY, TO SCALE, FBC
 107. BOTTOM AND TOP PLATES NOT SPECIFIED.
  
 5. SPECIFICATION FOR STRAPS/TIES TO BE SPECIFIC TO
 BRAND AND MODEL NUMBER TO SHOW RESISTANCE TO WIND
 LOADS, FBC 2010 RESIDENTIAL 301.
  
 6. BOND BREAK REQUIRED FBC 2010 RESIDENTIAL 703.6.3.
  
  
  
  
  
  