Plan Review Notes For Permit 14020705 |
Permit Number |
14020705 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-02-20 12:24:54 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PRODUCT APPROVAL FOR PEEL AND STICK IS INCOMPLETE; | | SUBMIT ALL APPLICABLE PAGES (INCLUDING GENERAL | | LIMITATIONS, SYSTEM COMPONENT DESCRIPTION, COVER SHEET | | WHICH WILL INCLUDE STATUS AND PRODUCT APPROVAL NUMBER, | | AND ANY OTHER SHEETS NEEDED TO DETERMINE CODE | | COMPLIANCE). | | | | 2. ENGINEERING REQUIRED FOR ENHANCED FASTENING AS THE | | ASSEMBLY SELECTED DOES NOT COMPLY WITH ZONES 2 &3. SEE | | ITEM 8 OF THE PRODUCT APPROVAL. | | | | |
|