2014-03-16 11:39:17 | MINIMUM PLAN REVIEW CRITERIA. FBC- 107.3.5.3 ? | | | | PROVIDE LOAD CALCULATIONS BASED ON THE NEW ACTUAL | | CONNECTED LOAD. CALCULATIONS INDICATE 2 SMALL APPLIANCE | | KITCHEN CIRCUITS. THIS SHOULD BE REMOVED AS A KITCHEN | | MAY NOT BE PERMITTED WITHIN THE STRUCTURE. THE LOAD | | CALCULATIONS SHOULD INDUCATE THE EXISTING SERVICE IS | | ADEQUATE TO ACCOMODATE THE NEW, ALTHOUGH SMALL, | | PROPOSED LOAD. NOTE INDICATES GFI FOR BATH AREA, NO GFI | | TO SERVICE BATH IS PROVIDED. | | |
|