Plan Review Notes
Plan Review Notes For Permit 14020551
Permit Number 14020551
Review Stop B
Sequence Number 3
Notes
Date Text
2014-08-06 16:08:37BUILDING PROVISO:
  
 SHEET AE101B & AE101F THE MAIN ENTRY GATE BETWEEN THE
 FITNESS CENTER & BISTRO WILL NEED TO MEET BOTH
 REQUIREMENTS FOR EGRESS:
  
 2010 FBC-B 424.1.3.1.9. ACCESS THROUGH THE BARRIER OR
 FENCE FROM DWELLING UNITS, SUCH AS HOMES, APARTMENTS,
 MOTEL ROOMS AND HOTEL ROOMS, SHALL BE THROUGH
 SELF-CLOSING, SELF-LATCHING LOCKABLE GATES OF 48 INCH
 (1219 MM) MINIMAL HEIGHT FROM THE FLOOR OR GROUND WITH
 THE LATCH LOCATED A MINIMUM OF 54 INCHES (1372 MM) FROM
 THE BOTTOM OF THE GATE OR AT LEAST 3 INCHES (76 MM)
 BELOW THE TOP OF THE GATE ON THE POOL SIDE. IF THE
 SELF-CLOSING, SELF-LATCHING GATE IS ALSO SELF-LOCKING
 AND IS OPERATED BY A KEY LOCK, ELECTRONIC OPENER OR
 INTEGRAL COMBINATION LOCK, THEN THE OPERABLE PARTS OF
 SUCH LOCKS OR OPENERS SHALL BE 34 INCHES MINIMUM (864
 MM) AND 48 INCHES MAXIMUM (1219 MM) ABOVE THE FINISHED
 FLOOR OR GROUND. GATES SHALL OPEN OUTWARD AWAY FROM THE
 POOL AREA.
  
 2010 FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 THE GATES WILL NEED TO BE DESIGNED SO PANIC HARDWARE
 (1008.1.10) WILL BE INSTALLED ON THE INTERIOR SIDE OF
 THE GATE AND THE EXTERIOR SIDE WILL HAVE A RELEASING
 MECHANISM LOCATED AT 54 INCHES ABOVE THE
 DECK(424.1.1.9) . THE RELEASING MECHANISM WILL NEED TO
 BE TIED INTO THE PANIC HARDWARE RELEASING MECHANISM.
 NOTE THE CONCERNS OF A CHILD ON THE EXTERIOR SIDE OF
 THE GATE WILL NOT BE ABLE TO ACTIVATE THE PANIC
 HARDWARE AND GAIN ENTRY INTO THE POOL AREA. THE GATE
 WILL HAVE TO HAVE SELF CLOSING AND SELF LATCHING
 HARDWARE.
  
 THIS TYPE OF SITUATION WILL NEED TO BE ADDRESSED ON ALL
 GATES AND OR DOORS THAT LEAD TO THE POOL DECK FROM THE
 EXTERIOR.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676