Plan Review Notes For Permit 14020547 |
Permit Number |
14020547 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2014-06-11 15:47:03 | ****PROVISOS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER, [email protected], | | 561-805-6724 | | 1. PER APPLICANT, SCOPE OF THIS FOUNDATION PERMIT IS | | LIMITED TO VIBROCOMPACTION, BELOW GRADE FOUNDATIONS, | | AND WATER, SEWER AND STORM PIPING. | | 2. PER APPLICANT, PLAT PLAN HAS BEEN SUBMITTED. | | 3. FBC 110.7 IMPACT OF CONSTRUCTION. PER MANNY | | GONZALEZ, A POLLUTION PREVENTION PLAN HAS BEEN FILED | | WITH THE ENGINEERING DEPARTMENT. | | 4. INFORMATIONAL SHEETS NOT RELATED TO FOUNDATION HAVE | | NOT BEEN REVIEWED. | | 5. REVISE SHEET S5.1, TYPICAL CONCRETE COLUMN, TO | | REMOVE TEXT RELATED TO PILE CAPS. | | 6. PRIOR TO RESUBMITTAL OF THE BUILDING PLANS, PERMIT | | 14030096, PLEASE CONTACT CAROLINE PUELL, 561.805.6659, | | [email protected] TO DISCUSS NAMING CONVENTION FOR THE | | FILES. FOUNDATION PLAN SHEETS WERE NOT NAMED IN A | | MANNER WHICH IS EXPEDITIOUS FOR PLAN REVIEW. MS. PUELL | | IS ABLE TO GIVE GUIDANCE IN THIS AREA. | | |
|